143
Notes:
1. Between 55° and 74°C, the unit is de-rated to a maximum load of
1600VA/1200W.
2. De-rate operating temperature above 4900 FT (1500m) by 5° C per each
additional 1000 ft (3000m).
Note: Specifications subject to change without notice.
Output Apparent Power, VA
)
Inverter Mode) 2000 (Line Mode
2000 (
Output Active Power, W
1500 (
Inverter Mode) 1500
)
Line Mode
(
Power Factor
0.75
Input Frequency, Hz +/
-
3HZ
60
Input Voltage Range, VAC
90
to 150 VAC User programmable. Defaults set
@ 100 ~ 130 VAC +/
-
2 VAC.
Output Voltage
Nom (Tolerances are user programmable
)
120
Inverter Mode
120
VAC+/
-
%
5
Maximum Input Current, A
30
Transformer
Linear (Non
-
Isolated)
Transfer Time, msec
<65
msec. Buck & Boost enabled <10 msec.
Inrush Current
Load dependant
Output Waveform THD, %
(Resistive Load
<3
)
Load Crest Ratio
3:1
Efficiency, Lin
e Mode
)
95% (Resistive Load
>
Efficiency, Inverter Mode
>
)
80% (Resistive Load
Nominal Battery String
VDC Voltage, VDC
48
Step Load Response (50%)
1
Cycle full recovery
Over Current Protection
Double Pole Single Throw Circuit Breaker Rated
at
30
Amp for input and output DC Bus: 60 Amp
circuit breaker
Transient Suppression
MOV transient suppression elements (>150V)
DC Power
Drawn from batteries
Electrical Specifications
Notes:
Содержание MP Series
Страница 3: ...III ...
Страница 20: ...20 STEP 1 Connect CONTROL Wires ...
Страница 22: ...22 Installation and Troubleshooting Guide Figure 9 ...
Страница 30: ...30 MP2000E System Battery Backup System Section 2 Operator s Manual ...
Страница 49: ...49 Figure 21 Note See Section 2 2 14 For details on Event Log View under Maintenance submenu ...
Страница 51: ...51 2 2 8 Status Submenu CONT D ...
Страница 70: ...70 2 3 3 Main Menu ...
Страница 72: ...2 3 4 1 RS232 USB Menu Tree ...
Страница 74: ...74 ...
Страница 104: ...104 Figure 6 70 SMS for Event Log Screen ...
Страница 126: ...126 ...
Страница 148: ...148 ...