98
than bypassing VAC power through the power transfer switch ( PTS). Figures 6-60
and 6-61 show the AVR Off Settings and AVR On Settings screens.
Figure 6-60: AVR Off Settings Form
Figure 6-61: AVR On Settings Form
Figure 6-62 describes the fields in the forms.
FIELD
DETAILS
High Voltage
Transfer Point
Setting
This is the VAC input voltage level at which the UPS switches
from On Line to On Battery.
High Limit
Point
VAC voltage setting at which the UPS switches from On Line to
On Battery.
High Hyst
Point
High Hysteresis Point
— This is the VAC voltage level down to
which the VAC input must lower ( after being above High Limit
Point ) before qualifying for On Line operation.