57
2.2.13 Fault Menu
Purpose: Describes the Fault Submenu and how to use the LCD for troubleshooting.
(Figures 25, 26 and 27)
Procedure: When the red ALARM LED is continuously ON, the unit has a fault,
indicating a condition where backup power is unavailable. Press ENTER to display
fault description.
TIP: When the unit has a fault and line power is qualified and available, the output
loads are directly connected to the Input line with no line conditioning or backup
power provided.
LCD SHOWS
FAULT
DESCRIPTION
Short Circuit
Short Circuit
The load is short-circuited or the inverter did not start
Batt. Low Volt
Low Battery Voltage*
The battery's output voltage is low
Batt. High Volt
High Battery Voltage
The battery's output voltage is high
Temp High
High Temperature*
The battery's temperature or the MP2000 internal
temperature is high
Overload
Overload
The loads are drawing more power than the MP2000
can provide
Figure 27
Fault Table
*These faults are self-resetable. After the fault condition is removed, the unit
automatically returns to Line mode if the line is qualified or Battery mode if it isn’t. For
the other faults, the unit is reset by shutting it down and restarting, using AC & battery
breakers. The faults can also be reset in the Control Menu of the LCD display.
Содержание MP Series
Страница 3: ...III ...
Страница 20: ...20 STEP 1 Connect CONTROL Wires ...
Страница 22: ...22 Installation and Troubleshooting Guide Figure 9 ...
Страница 30: ...30 MP2000E System Battery Backup System Section 2 Operator s Manual ...
Страница 49: ...49 Figure 21 Note See Section 2 2 14 For details on Event Log View under Maintenance submenu ...
Страница 51: ...51 2 2 8 Status Submenu CONT D ...
Страница 70: ...70 2 3 3 Main Menu ...
Страница 72: ...2 3 4 1 RS232 USB Menu Tree ...
Страница 74: ...74 ...
Страница 104: ...104 Figure 6 70 SMS for Event Log Screen ...
Страница 126: ...126 ...
Страница 148: ...148 ...