43
The following mode may be programmed by the User
(see Section 2.2.10)
Sense Type (Generator / Normal Mode)
This is used to broaden the input
parameters to accommodate the
voltage fluctuations created by a
backup generator or a noisy line.
The factory default setting is normal,
where the unit runs on normal
parameters. Switching to Generator
makes it run on noisy generator
parameters.
If the unit constantly switches
between
line and battery modes due to a noisy
line, select generator mode to
prevent
unnecessary transfers / returns.
Normal Line
Generator or Noisy
Line
Generator Parameters
Normal Parameters
Line Mode
Normal Parameters
Generator Parameters
Normal and Generator Parameters