8 Operation
Maschinenfabrik Reinhausen GmbH 2018
90
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Parameter
Option
UI measuring channels
3-ph. voltage, 1-ph. current
Measurement mode
Phase-phase
Table 26: Circuit K
Setting voltage-transformer circuit
You can use this parameter to set your voltage transformer's circuit. You can
select the following options:
Option
Description
1 Ph phase voltage
Measurement in 1-phase grid between
the conductor and neutral conductor.
3 Ph differential voltage
Measurement in 3-phase grid between 2
conductors
3 Ph phase voltage
Measurement in 3-phase grid between
conductor and neutral conductor
Table 27: Voltage-transformer circuit
To set the voltage-transformer circuit, proceed as follows:
1. Go to
Settings > Parameters > Transformer data > Voltage-trans-
former circuit
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Setting current-transformer circuit
You can use this parameter to set the circuit for your current transformer.
You can select the following options:
Option
Description
1 Ph phase current
Measurement of phase current in 1-phase
grid.
3 Ph total current
Measurement of differential current in 3-
phase grid.
3 Ph phase current
Measurement of phase current in 3-phase
grid.
Table 28: Current-transformer circuit
To set the current-transformer circuit, proceed as follows:
1. Go to
Settings > Parameters > Transformer data > Current-trans-
former circuit
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.