7 Commissioning
Maschinenfabrik Reinhausen GmbH 2018
60
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Figure 45: Perform a ground test on the G1 PULS DIMENSION QS3.241 assembly
7.1.2 Performing a dielectric test
The device is tested before delivery. Note the following points if you would
like to perform a dielectric test:
NOTICE
Damage to the device!
A dielectric test with a test voltage that is greater than the maximum permit-
ted test voltage can lead to the device being damaged.
► Perform the dielectric test with a test voltage that is less than or equal to
the maximum permitted test voltage.
► Perform the dielectric test using the permitted interfaces only.
Depending on the device configuration, you may only test the assemblies
listed below. You may not test any other assemblies.
Assembly
Interfaces
Test parameters
Max. test voltage
Max. test dura-
tion
Ramp
Breaking current
threshold
UI 3
N, L1, L2, L3
k1, l1, k2, l2, k3, l3
2.2 kV AC
2 s
5 s
> 4 mA
G1 (PULS)
N, L
> 4 mA
Table 10: Permitted interfaces and test parameters for the dielectric test