8 Operation
Maschinenfabrik Reinhausen GmbH 2018
135
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Deleting a configuration
If necessary, you can delete the data point configuration. To do so, proceed
as follows:
1. Go to
Settings > Mapping
.
2. Select the desired
function
.
3. Press the
Delete
button to delete the configuration.
8.11.7 Configure data points (optional)
You can use the optional "Configure data points" function to adjust the con-
trol system data points of the device. You can only configure the data points
on a PC using the web-based visualization.
8.11.7.1 Configuring IEC 60870-5-101 data points
You can adjust the following data point properties for the IEC 60870-5-101
control system protocol:
Column
Description
Modifiable
Setting range
Active
You can use the checkbox to set whether the data point is
to be transferred via the control system protocol or not.
Yes
Active/inactive
IOA
Data point address. The setting range is based on the set-
ting for the "Octet number of information object address"
parameter (octet 2 or 3).
Yes
Octet 2: 1...65,535
Octet 3:
1...16,777,215
Name
Data point designation.
No
-
Type
Data point type.
No
-
Group
Data point group or groups. You must enter the group
membership as a binary code (5 bits). A maximum of 5
groups is possible. Example:
▪ 00000: belongs to no groups
▪ 00001: group 1
▪ 01000: group 4
▪ 01001: group 1 and group 4
Yes
00000...11111
INTG
The value indicates whether the data point is to be in-
cluded in a general query (1) or not (0).
Yes
0, 1