3 IT security
Maschinenfabrik Reinhausen GmbH 2018
19
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Figure 1: Interfaces of the CPU assembly
Interface
Protocol
Port
Description
CAN 1
-
-
Attachment of the DIO assembly
CAN 2
-
-
Communication with other ISM® devices
(e.g. parallel operation)
COM 1
-
-
Internal system interface
COM 2
-
-
Serial interface (SCADA)
USB
-
-
Import or export of data
ETH 1
TCP
102
IEC 61850
2)
ETH 1
TCP
502
Modbus
2)
ETH 1
TCP
20000
DNP3
2)
ETH 1
UDP
67
DHCP server
ETH 2.x
TCP
21
FTP
1)
(only for MR service)
ETH 2.x
TCP
80
HTTP for web-based visualization
1)
ETH 2.x
TCP
443
HTTPS for web-based visualization
1)
ETH 2.x
TCP
990
FTPS (only for MR service)
ETH2.x
TCP
8080
HTTP for web-based visualization
1)
ETH2.x
TCP
8081
HTTPS for web-based visualization
1)
Table 4: Interfaces and open ports of the CPU assembly
1)
Port is closed if you activate the device's SSL encryption.
2)
Default setting; if you have modified the port for the control system proto-
col, only the set port is opened.