8 Operation
Maschinenfabrik Reinhausen GmbH 2018
87
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Circuit G
▪ Three-phase measurement.
▪ The voltage transformers are connected between the phases.
▪ The current lags behind the voltage by 30°.
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-
Phase angle correction
0°
UI measuring channels
3-phase measurement (channels 1, 2, 3)
Measurement mode
Phase-phase
Table 22: Circuit G
Circuit H
▪ Three-phase measurement.
▪ The voltage transformers are connected between the phase and neutral
conductor.
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-