8 Operation
Maschinenfabrik Reinhausen GmbH 2018
119
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
To set tap position monitoring, proceed as follows:
1. Go to
Settings > Parameters > Tap position monitoring
.
2. Select the parameter you want.
3. Set parameter.
4. Press the
Accept
button to save the modified parameter.
8.11 SCADA
The following section describes how you can configure the device to connect
to a control system (SCADA). You can download the data points with the
help of the export manager [
8.11.1 Configuring IEC 61850 (optional)
If you want to use the IEC 61850 control system protocol, you must set the
following parameters.
Figure 78: Setting parameters for IEC 61850
IP address
You can use this parameter to assign an IP address to the device.
To set the IP address, proceed as follows:
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connec-
tion.
1. Go to
Settings > Parameters > IEC
61850 > IP address
.
2. Enter IP address.
3. Press the
Accept
button to save the modified parameter.