8 Operation
Maschinenfabrik Reinhausen GmbH 2018
93
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
8.6.4 Setting the display for the power factor
This parameter lets you set whether the device is to display a negative
power factor. You can select the following options:
Option
Description
Off
The power factor is always shown as positive.
P > 0
The power factor is shown as negative if the active power is
positive.
P < 0
The power factor is shown as negative if the active power is
negative.
Q > 0
The power factor is shown as negative if the reactive power is
positive.
Q < 0
The power factor is shown as negative if the reactive power is
negative.
Table 30: Setting the display for the power factor
To set the power factor display, proceed as follows:
1. Go to
Settings > Parameters > Measurement > Negative power factor
display
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
8.7 Line drop compensation
You can use the compensation function to compensate for the load-depen-
dent voltage drop between the transformer and consumer. The device pro-
vides 2 methods of compensation for this purpose:
▪ R&X compensation
▪ Z compensation
Figure 61: Setting line drop compensation