8.18 Linking signals and events
The devices allows you to link control system commands (SCADA) with de-
vice functions, and events with control system messages.
The system commands available are each permanently linked to a
Generic
SCADA command
event message for this purpose.
Command
Event message
Generic SCADA command 1
Generic SCADA command 1
Generic SCADA command 2
Generic SCADA command 2
...
...
Generic SCADA command 10
Generic SCADA command 10
Table 61: Linking of control system commands with event messages
You can link the event messages to device functions and control system
messages. You can also link all other event messages (e.g.
Undervoltage
U<
) to control system messages. Corresponding parameters, for which you
need to enter the relevant event number, are provided for this purpose.
8.18.1 Linking functions
You can link the
Generic SCADA command
events to device functions. This
allows you to remotely control the device via the control system (SCADA).
Depending on your device configuration, the following parameters are avail-
able for this purpose:
Parameters
Description
Master parallel operation method
If the assigned event is active, the device
activates the master parallel operation
method.
Follower parallel operation method
If the assigned event is active, the device
activates the follower parallel operation
method.
Automatic tap synchronization parallel
operation method
If the assigned event is active, the device
activates the automatic tap synchroniza-
tion parallel operation method.
Independent regulation
If the assigned event is active, the device
activates simplex mode.
Deactivate parallel operation
If the assigned event is active, the device
deactivates parallel operation.
Blocking
If the assigned event is active, automatic
voltage regulation is blocked.
Activate remote mode
If the assigned event is active, the device
activates remote mode.
High-speed return
If the assigned event is active, the device
activates high-speed return.