8 Operation
Maschinenfabrik Reinhausen GmbH 2018
88
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Parameter
Option
Phase angle correction
0°
UI measuring channels
3-phase measurement (channels 1, 2, 3)
Measurement mode
Phase-neutral
Table 23: Circuit H
Only use the circuits I, J and K on symmetrical grids. Otherwise the device
will calculate incorrect performance values.
Circuit I
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phases.
▪ The current transformer is connected to phase L1.
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-
Phase angle correction
-30°
UI measuring channels
3-ph. voltage, 1-ph. current
Measurement mode
Phase-phase
Table 24: Circuit I