8 Operation
Maschinenfabrik Reinhausen GmbH 2018
120
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Subnet mask
You can use this parameter to set the subnet mask.
Be sure to enter a valid network mask that is not 0.0.0.0, otherwise it will not
be possible to connect to the device.
To set the subnet mask, proceed as follows:
1. Go to
Settings > Parameters > IEC
61850 > Subnet mask
.
2. Enter subnet mask.
3. Press the
Accept
button to save the modified parameter.
Gateway address
You can use this parameter to set the gateway's IP address.
If you set the value to 0.0.0.0, no gateway is used.
To set the gateway address, proceed as follows:
1. Go to
Settings > Parameters > IEC
61850 > Gateway address
.
2. Enter gateway address.
3. Press the
Accept
button to save the modified parameter.
IED name
You can use this parameter to assign the device an IED name in order for it
to be identified in the IEC 61850 network.
The IED name must start with a letter and may contain no more than 11
characters.
To set the IED name, proceed as follows:
1. Go to
Settings > Parameters > IEC
61850 > IED name
.
2. Enter IED name.
3. Press the
Accept
button to save the modified parameter.
Device ID
You can use this parameter to assign the device a device ID in order for it to
be identified in the IEC 61850 network.
To set the device ID, proceed as follows:
1. Go to
Settings > Parameters > IEC
61850 > Device ID
.