8 Operation
Maschinenfabrik Reinhausen GmbH 2018
89
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Circuit J
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phases.
▪ The current transformer is connected to phase L2.
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-
Phase angle correction
-150°
UI measuring channels
3-ph. voltage, 1-ph. current
Measurement mode
Phase-phase
Table 25: Circuit J
Circuit K
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phases.
▪ The current transformer is connected to phase L3.
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-
Phase angle correction
90°