1.
Configure the power supply for remote operation using the front panel commands
described in Section 3.1.1.3 and 3.1.2.2 for DPD and DPA Series power supplies,
respectively.
2.
Connect a 9-conductor straight through, D-subminiature cable between the computer
interface and connector JS3 at the rear of the power supply.
3.
Verify the availability of the RS232 port selected.
4.
Turn on the power switch of the DP Series power supply and turn on the IBM PC or
compatible computer.
5.
Start the HyperTerminal test software and set the COM port to the one connected to the
DP Series power supply. Configure the terminal for 19200, N, 8, 1. Set the terminal to
echo typed characters locally and “append line feeds to incoming line ends.” (The echo
feature is not functional with Windows 98.)
6.
Type the query command “*IDN?” in the output data window and press enter. The text
should be entered inside the quotation marks.
7.
As illustrated in figure 4.1, the returned data will display the following:
“Magna-Power Electronics, Inc., DPD16-900, SN: 1163-0361” where the model and
serial number may be different depending on the unit being tested.
8.
Verify that the model number in the *IDN? response corresponds to the power supply
under test. If this is not the case, configure the supply using the steps outlined in Section
4.3.9.1 CAL:IDN.
9.
With the output terminals of the power supply open, enter the command VOLT xx where
xx is 50% of rated voltage and press enter. Press the display key on the front panel of the
power supply and verify that the set point is 50% of rated voltage.
10.
Enter the command OUTP:START and press enter. The power supply’s contactor should
close with an audible click and the front panel indicators and meters should indicate
power flow. Verify that the power supply’s output voltage is equal to the VOLT setting
set in the previous command.
11.
Enter the command MEAS:VOLT? and press enter. Verify the output voltage
corresponds the voltmeter on the front panel of the power supply.
12.
Enter the command OUTP:STOP and press enter. The power supply’s contactor should
open with an audible click and the front panel indicators and meters should indicate
operation in a standby state.
4.3
SCPI Subsystem Commands
The SCPI command set is broken down into sub-systems as described in the following Sections
of this chapter. The syntax for data formats of the SCPI command set is defined in Section
4.3.15.
4.3.1
Source Subsystem
This subsystem programs the voltage set point, current set point, over voltage trip, over current
trip, and period of the power supply.
64
Содержание DP SERIES II
Страница 1: ...OPERATING AND SERVICE MANUAL DP SERIES II DC POWER SUPPLIES...
Страница 2: ......
Страница 3: ...MAGNA POWER ELECTRONICS INC 39 ROYAL ROAD FLEMINGTON NJ 08822 January 6 2010...
Страница 4: ......
Страница 6: ...improper use of the equipment and accessories ii...
Страница 28: ...Figure 1 2 DP Series air cooled 10 kW to 30 kW package drawing with D Version front panel 15...
Страница 29: ...Figure 1 3 DP Series water cooled 10 kW to 30 kW package drawing with D Version front panels 16...
Страница 39: ...Figure 2 3 DPC Series controls and indicators Energizes control circuits without turning on main power 26...
Страница 44: ...Figure 3 2 Set voltage output at memory displayed Figure 3 3 Set current output at memory displayed 31...
Страница 45: ...Figure 3 4 Set over voltage trip at memory displayed Figure 3 5 Set over current trip at memory displayed 32...
Страница 47: ...Figure 3 7 Set remote sense Figure 3 8 Set internal control 34...
Страница 48: ...Figure 3 9 Set external control Figure 3 10 Set rotary input 35...
Страница 49: ...Figure 3 11 Set keypad input Figure 3 12 Set external program input 36...
Страница 50: ...Figure 3 13 Set remote input Figure 3 14 Set external interlock 37...
Страница 53: ...Figure 3 15 Calibration 40...
Страница 56: ...Figure 3 17 Set remote sense Figure 3 18 Set internal control Figure 3 19 Set external control 43...
Страница 57: ...Figure 3 20 Set rotary input Figure 3 21 Set external program input Figure 3 22 Set remote input 44...
Страница 61: ...Figure 3 24 Calibration 48...
Страница 63: ...Figure 3 25 a Local and b remote sensing 50...
Страница 64: ...Figure 3 26 External a resistive b voltage and current programming 51...
Страница 111: ...98...
Страница 113: ...Figure 5 1 Configuration setup Figure 5 2 GPIB communications setup 100...
Страница 118: ...Figure 5 7 Register Panel Figure 5 8 Calibration Panel 105...
Страница 119: ...Figure 5 9 Firmware Panel Figure 5 10 Modulation Panel for Version D models only 106...
Страница 121: ...Figure 6 1 Block diagram 108...
Страница 128: ...source Figure 8 2 Leadless remote sensing Figure 8 3 IV characteristics for a typical photovoltaic array 115...
Страница 139: ...Figure B 1 Information Panel Figure B 2 Configure Panel 126...
Страница 140: ...Figure B 3 Reboot in Progress Panel Figure B 4 Web Control Panel 127...
Страница 145: ...Figure D 1 RS485 a 2 wire and b 4 wire connections 132...