![MPE DP SERIES II Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/mpe/dp-series-ii/dp-series-ii_operating-and-service-manual_1843048070.webp)
3.8
Parallel Operation
Two or more DP Series power supplies can be connected in parallel to obtain a total output
current greater than that available from one power supply. The total output current is the sum of
the output currents of the individual power supplies. Each power supply can be turned on or off
separately.
A parallel connection involves attaching the positive terminals of all supplies to be paralleled to
the positive point of the load and attaching the negative terminals to the negative point of the
load. The output current controls of each power supply can be separately set. The output
voltage control of one power supply (master) should be set to the desired output voltage; the
other power supply (slave) should be set for a slightly higher output voltage. The master will
act as a constant voltage source; the slave will act as a constant current source, dropping its
output voltage to equal that of the master.
3.9
Series Operation
Two or more power supplies, or master/slave modules, can be connected in series to obtain a
total output voltage greater than that available from one power supply. The total output voltage
is the sum of the output voltage of the individual power supplies. Each power supply can be
turned on or off separately. The master/slave modules turn on and off together when the slave’s
external control is enabled.
Caution: No plus or minus voltage should exceed 1000 Vdc with respect to
ground for models rated 1000 V less. No plus or minus voltage should exceed
4000 Vdc with respect to ground for models rated greater than 1000 V.
3.9.1
Series Operation - Direct
The simplest series connection involves attaching the negative terminal of the first supply, or
master/slave module, to the positive terminal of the second supply. An output shorting jumper is
provided for interconnecting the modules. The load is connected between the positive terminal
of the first supply and the negative terminal of the second supply. The output current controls of
each power supply are operative and the current limit is equal to the lowest control setting. If
any one output current control is set too low with respect to the total output current, the series
power supplies will automatically crossover to constant current operation and the output voltage
will drop.
3.9.2
Series Operation - Master/Slave
Master/slave series operation permits equal voltage sharing under all load conditions and allows
complete control of output voltage from one master power supply.
57
Содержание DP SERIES II
Страница 1: ...OPERATING AND SERVICE MANUAL DP SERIES II DC POWER SUPPLIES...
Страница 2: ......
Страница 3: ...MAGNA POWER ELECTRONICS INC 39 ROYAL ROAD FLEMINGTON NJ 08822 January 6 2010...
Страница 4: ......
Страница 6: ...improper use of the equipment and accessories ii...
Страница 28: ...Figure 1 2 DP Series air cooled 10 kW to 30 kW package drawing with D Version front panel 15...
Страница 29: ...Figure 1 3 DP Series water cooled 10 kW to 30 kW package drawing with D Version front panels 16...
Страница 39: ...Figure 2 3 DPC Series controls and indicators Energizes control circuits without turning on main power 26...
Страница 44: ...Figure 3 2 Set voltage output at memory displayed Figure 3 3 Set current output at memory displayed 31...
Страница 45: ...Figure 3 4 Set over voltage trip at memory displayed Figure 3 5 Set over current trip at memory displayed 32...
Страница 47: ...Figure 3 7 Set remote sense Figure 3 8 Set internal control 34...
Страница 48: ...Figure 3 9 Set external control Figure 3 10 Set rotary input 35...
Страница 49: ...Figure 3 11 Set keypad input Figure 3 12 Set external program input 36...
Страница 50: ...Figure 3 13 Set remote input Figure 3 14 Set external interlock 37...
Страница 53: ...Figure 3 15 Calibration 40...
Страница 56: ...Figure 3 17 Set remote sense Figure 3 18 Set internal control Figure 3 19 Set external control 43...
Страница 57: ...Figure 3 20 Set rotary input Figure 3 21 Set external program input Figure 3 22 Set remote input 44...
Страница 61: ...Figure 3 24 Calibration 48...
Страница 63: ...Figure 3 25 a Local and b remote sensing 50...
Страница 64: ...Figure 3 26 External a resistive b voltage and current programming 51...
Страница 111: ...98...
Страница 113: ...Figure 5 1 Configuration setup Figure 5 2 GPIB communications setup 100...
Страница 118: ...Figure 5 7 Register Panel Figure 5 8 Calibration Panel 105...
Страница 119: ...Figure 5 9 Firmware Panel Figure 5 10 Modulation Panel for Version D models only 106...
Страница 121: ...Figure 6 1 Block diagram 108...
Страница 128: ...source Figure 8 2 Leadless remote sensing Figure 8 3 IV characteristics for a typical photovoltaic array 115...
Страница 139: ...Figure B 1 Information Panel Figure B 2 Configure Panel 126...
Страница 140: ...Figure B 3 Reboot in Progress Panel Figure B 4 Web Control Panel 127...
Страница 145: ...Figure D 1 RS485 a 2 wire and b 4 wire connections 132...