the power supply. The Output frame can be cleared or saved to a file by pressing the clear button
or the save to file button.
Voltage Scale and Current Scale are not available to the user. These are factory specific
commands that require an alternate password to access.
5.6
Firmware Panel
The Firmware Panel is illustrated in figure 5.9. The Firmware Panel enables the program stored
internal to the power supply to be upgraded. The factory recommends that firmware upgrades be
performed only if there is an operational problem with the power supply.
The following steps list the procedure for upgrading the firmware:
1.
Turn the power supply off.
2.
Connect a RS232 cable between a serial port on a computer and connector JS3 on the
power supply.
3.
Press the select button and choose the file to be loaded.
4.
Press the start button. The Status frame will display “Initiating.”
5.
Turn on the power supply. If the supply is not turned on within 10 seconds, “Time Out”
will be displayed in the Status frame indicating communications is lost.
During the process of upgrading the firmware, the front panel of the power supply will remain
blank. After communications is established, the Status frame will initially display “Erasing” and
the Current Address frame will display the address in memory being erased. After the entire
memory is erased, the Status frame will display “Loading ” and the Current Address frame will
display the address in memory being loaded. The Status frame will display “Finished” and the
front panel display will return to normal after the memory is reprogrammed..
Pressing the stop button will terminate execution at any time.
5.7
Modulation Panel (D Version front panels only)
The Modulation Panel is illustrated in figure 5.10. The Modulation Panel enables a user to set and
view the modulation settings as described in Section 4.3.14. The modulation settings consist of
control input, modulation type (multiplication or addition), table row, modulation voltage input,
and modulation factor. The Modulation Panel provides the form to program a linear or piece-wise
linear lookup table for the selected modulation type. The lookup table can have a maximum of 50
data points. The modulation voltage input, VMOD, must be entered in ascending order. For
lookup tables with less than 50 data points, VMOD must be terminated with 9999. Any data
entered for modulation factor on the terminating row is ignored. The Output frame on the right of
the window displays all of the communications with the power supply. The Output frame can be
cleared or saved to a file by pressing the clear button or the save to file button.
104
Содержание DP SERIES II
Страница 1: ...OPERATING AND SERVICE MANUAL DP SERIES II DC POWER SUPPLIES...
Страница 2: ......
Страница 3: ...MAGNA POWER ELECTRONICS INC 39 ROYAL ROAD FLEMINGTON NJ 08822 January 6 2010...
Страница 4: ......
Страница 6: ...improper use of the equipment and accessories ii...
Страница 28: ...Figure 1 2 DP Series air cooled 10 kW to 30 kW package drawing with D Version front panel 15...
Страница 29: ...Figure 1 3 DP Series water cooled 10 kW to 30 kW package drawing with D Version front panels 16...
Страница 39: ...Figure 2 3 DPC Series controls and indicators Energizes control circuits without turning on main power 26...
Страница 44: ...Figure 3 2 Set voltage output at memory displayed Figure 3 3 Set current output at memory displayed 31...
Страница 45: ...Figure 3 4 Set over voltage trip at memory displayed Figure 3 5 Set over current trip at memory displayed 32...
Страница 47: ...Figure 3 7 Set remote sense Figure 3 8 Set internal control 34...
Страница 48: ...Figure 3 9 Set external control Figure 3 10 Set rotary input 35...
Страница 49: ...Figure 3 11 Set keypad input Figure 3 12 Set external program input 36...
Страница 50: ...Figure 3 13 Set remote input Figure 3 14 Set external interlock 37...
Страница 53: ...Figure 3 15 Calibration 40...
Страница 56: ...Figure 3 17 Set remote sense Figure 3 18 Set internal control Figure 3 19 Set external control 43...
Страница 57: ...Figure 3 20 Set rotary input Figure 3 21 Set external program input Figure 3 22 Set remote input 44...
Страница 61: ...Figure 3 24 Calibration 48...
Страница 63: ...Figure 3 25 a Local and b remote sensing 50...
Страница 64: ...Figure 3 26 External a resistive b voltage and current programming 51...
Страница 111: ...98...
Страница 113: ...Figure 5 1 Configuration setup Figure 5 2 GPIB communications setup 100...
Страница 118: ...Figure 5 7 Register Panel Figure 5 8 Calibration Panel 105...
Страница 119: ...Figure 5 9 Firmware Panel Figure 5 10 Modulation Panel for Version D models only 106...
Страница 121: ...Figure 6 1 Block diagram 108...
Страница 128: ...source Figure 8 2 Leadless remote sensing Figure 8 3 IV characteristics for a typical photovoltaic array 115...
Страница 139: ...Figure B 1 Information Panel Figure B 2 Configure Panel 126...
Страница 140: ...Figure B 3 Reboot in Progress Panel Figure B 4 Web Control Panel 127...
Страница 145: ...Figure D 1 RS485 a 2 wire and b 4 wire connections 132...