9-60 Manual # 42-02-2223
Reference
A6 Motor Submenu
MOTOR ID
Motor Identification
none
-pm default
-pm
def
-pm
default
RATED MOTOR
POWER
Sets rated power in horsepower (HP) or kilo-
watts (kW) of motor. Value obtained from
motor nameplate.
HP
1.0 – 500.0
0.0
*
kW
0.75 – 400.00 0.00
*
RATED MTR VOLTS Sets rated motor voltage. Value obtained from
motor nameplate.
Volts
85.0 – 575.0
0.0
*
RATED MOTOR
CURR
Sets rated motor current. Value obtained from
motor nameplate.
Amps
1.00 – 800.00 0.00
*
MOTOR POLES
Sets number motor poles. MUST be even num-
ber or Setup Fault #3 will occur. Value
obtained from motor nameplate or calculated
from motor excitation frequency and rated
motor speed.
None
2 – 128
0
*
RATED MTR SPEED Sets rated rpm of Motor. Function of motor
only. Does not need to match Control Mtr
Speed setting. Value obtained from motor
nameplate.
RPM
18.0 – 3000.0 0.0
*
D AXIS INDUCT
Sets amount of inductance in flux producing
equivalent circuit of vector controlled PM
motor. Higher inductances used for higher
horsepower motors. Obtain from motor speci-
fications.
mH
0.50 – 50.00
10.00 *
Q AXIS INDUCT
Sets amount of inductance in torque producing
equivalent circuit of vector controlled PM
motor. Higher inductances used for higher
horsepower motors. Obtain from motor speci-
fications.
mH
0.50 – 50.00
10.00 *
STATOR RESIST
Sets amount of resistance in motor stator as a
percent of BASE IMPEDANCE, D2 which
appears in the Power Data display.
%
0.0 – 20.0
7.0
*
MOTOR IRON LOSS Sets motor iron loss at rated frequency. Units
in percent of rated power.
%
0.0 – 15.0
0.0
0.0
MOTOR MECH LOSS Sets motor mechanical losses at rated fre-
quency. Units in percent of rated power.
%
0.0 – 15.0
1.0
1.0
OVLD START LEVEL Defines maximum current at which motor can
run continuously without triggering motor
overload
%
100 – 150
110
110
OVLD TIME OUT
Motor Overload Time out. Defines amount of
time before motor overload alarm occurs when
motor is running at current level defined OVLD
Start Level+40% rated motor current
sec
5.0 – 120.0
60.0 60.0
TRQ CONST SCALE Torque constant scale. Drive automatically cal-
culates torque constant. Value can scale calcu-
lated torque constant for better performance.
None
0.50 – 2.00
0.78
0.78
ENCODER ANG
OFST
Encoder Angle Offset. Contains value of align-
ment determined during alignment procedure.
None
0 – 25000
Table 10. Quattro PM Elevator Drive, iControl
Содержание Nidec iControl
Страница 1: ...MOTION CONTROL ENGINEERING User Guide iControl with AC Drive...
Страница 15: ......
Страница 23: ...1 8 Manual 42 02 2223 iControl Overview...
Страница 75: ...2 52 Manual 42 02 2223 Construction Mode...
Страница 89: ...3 14 Manual 42 02 2223 Inspection Mode...
Страница 138: ...4 49 Safety Tests iControl AC 4 Figure 4 6 Typical Brake Test Circuit Machine Brake Emergency Brake...
Страница 280: ...6 95 iControl Circuit Board Quick References iControl AC 6 Figure 6 7 Earthquake Board Supporting Information...
Страница 303: ...6 118 Manual 42 02 2223 Troubleshooting...