9-58 Manual # 42-02-2223
Reference
A4 Motor Side Power Converter
Id REG DIFF GAIN Differential gain for current regulator flux gen-
eration. Meant for advanced operation.
RARELY needs to be changed from default.
Locked by ENGR PARM LOCK, C1.
None
0.00 – 0.40
0.00
0.00
Iq REG PROP GAIN Proportional gain for current regulator flux
generation. Advanced operation. RARELY
needs to be changed from default.
None
0.150 – 3.000
0.700 0.700
Id REG INTGRL
GAIN
Internal gain for current regulator flux genera-
tion. Advanced operation. RARELY needs to be
changed from default.
None
0.00 – 2.00
1.00
1.00
Iq REG DIFF GAIN Differential gain for current regulator of motor
torque. Advanced operation. RARELY needs to
be changed from default value. Locked by
ENGR PARM LOCK, C1.
None
0.00 – 0.40
0.00
0.00
lq REG PROP GAIN Proportional gain for current regulator torque
generation. Advanced operation. RARELY
needs to be changed from default value.
None 0.150 – 3.000
0.700 0.700
lq REG INTG GAIN
Integral gain for current regulator torque gen-
eration. Advanced operation. RARELY needs to
be changed from default value.
None
0.00 – 2.00
1.00
1.00
PWM FREQUENCY
Sets PWM or carrier frequency of motor arma-
ture portion of drive
kHz
2.5 – 16.0
10.0 10.0
UV ALARM LEVEL
Under voltage alarm level. Sets level at which
under voltage alarm declared. Units in % of L-
L voltage
%
80 – 99
90
90
UV FAULT LEVEL
Under voltage alarm level. Sets level at which
under voltage fault occurs. Units in % of L-L
voltage
%
50 – 99
80
80
EXTERN REACTANCE Sets externally connected reactance (as a per-
centage of base impedance) between drive
and motor. Units in percent of base imped-
ance.
%
0.0 – 10.0
0.0
0.0
FINE TUNE OFST
Manual offset for absolute position feedback
for TESTING purposes. WARNING: Changing
this can lead to motor runaway. Should always
be set to ZERO for NORMAL OPERATION.
Locked by ENGR PARM LOCK, C1.
Deg
-75.00 - +75.00 0.00
0.00
ld REF THRESHOLD Magnetek personnel only. Used to manually
set non-zero current reference for flux produc-
tion.
None
0.00 – 0.20
0.00
0.00
FLUX WEAKEN RATE Determines slew rate of flux weakening con-
trols. The higher the value, the faster flux
weakening will respond to voltage limit. Set-
ting to zero will disable flux weakening.
None
0.000 – 1.000
0.000 0.000
FLUX WEAKEN LEV Determines how close to the voltage limit the
drive will get before it will flux weaken. Locked
by Engr Parm Lock C1.
None
0.70 - 1.00
0.95
0.95
ALIGN VLT FACTOR Open Loop Alignment Voltage Reference Scal-
ing Factor. Use to scale open loop voltage ref-
erence at initial phase of open loop alignment.
None
0.05 – 1.99
1.00
0.00
Table 10. Quattro PM Elevator Drive, iControl
Содержание Nidec iControl
Страница 1: ...MOTION CONTROL ENGINEERING User Guide iControl with AC Drive...
Страница 15: ......
Страница 23: ...1 8 Manual 42 02 2223 iControl Overview...
Страница 75: ...2 52 Manual 42 02 2223 Construction Mode...
Страница 89: ...3 14 Manual 42 02 2223 Inspection Mode...
Страница 138: ...4 49 Safety Tests iControl AC 4 Figure 4 6 Typical Brake Test Circuit Machine Brake Emergency Brake...
Страница 280: ...6 95 iControl Circuit Board Quick References iControl AC 6 Figure 6 7 Earthquake Board Supporting Information...
Страница 303: ...6 118 Manual 42 02 2223 Troubleshooting...