Indications for laying connection cables:
• The shielding cover must be greater than 70%
• Do not lay power and signal cables side by side, in particular not close to the power filter, and make sure they are physically
separate
• Avoid crossing power cables with signal cables if they are not in the same cable (for example for DR2020)
• Make sure no loops form in the cables. Keep the cables as short as possible and close the common potential correctly
• Keep the input power supply cables separate from those of the output power (for the DR2020)
4.3.2..2
Dissipation of DR2020 axes (in Watt)
% Rated Current
CH6 52 X X X XX
CH6 54 X X X XX
CH6 56 X X X XX
0
17
17
17
25
43
69
95
50
69
121
173
75
95
173
252
100
121
226
330
Note: the DR2020 normally installed externally to the panel must not be considered in the thermal calculation of
the panel itself.
CH6 58 X X X XX
17
121
226
330
434
2/4 Amp
4/8 Amp
6/12 Amp
8/16 Amp
Fig 4.2 Detail of connection between cables and EMC bracket
4.3.2. Thermal sizing of the board
4.3.2.1. Dissipation of the power supply unit
% Rated
current
Type L50
Type L150
0
25
35
25
75
150
50
125
250
75
175
350
100
225
450
MAR2-E-191