22
TM SmartCool One 5057724 v1.0_08_2022
Minimum Unit Clearances For Maintenance
Units
A
B
(1)
C
(2)
D
(3)
SO09
mm
900
640
600
Min. 600mm - Max. 1000mm
(+ 50mm feet adju/- 25mm)
Min. 23.6” - Max. 39.3”
(+2.0” feet adju/- 1”)
in
35.4
25.2
23.6
SO12
mm
900
940
600
in
35.4
37.0
23.6
SO15
mm
900
600
600
in
35.4
23.6
23.6
SO18
mm
900
600
600
in
35.4
23.6
23.6
SO22
mm
900
600
600
in
35.4
23.6
23.6
SO25
mm
900
600
600
in
35.4
23.6
23.6
SO31
mm
900
600
600
in
35.4
23.6
23.6
SO35
mm
900
600
600
in
35.4
23.6
23.6
SO30
mm
1200
600
600
Min. 650mm - Max. 1000mm
(+ 50mm feet adju/- 25mm)
Min. 25.6” - Max. 39.3”
(+2.0” feet adju/- 1”)
in
47.2
23.6
23.6
SO40
mm
1200
600
600
in
47.2
23.6
23.6
SO50
mm
1200
600
600
in
47.2
23.6
23.6
SO60
mm
1200
600
600
in
47.2
23.6
23.6
The minimum clearance requirements must be maintained around the units. This is to ensure filters can be maintained
from the front or side* of the unit and that fans can be maintained from the front of the unit. For below floor floor stand
installations, floor tile support posts must be removable to allow access to the fans.
* SO09 and SO12 require side access for filter removal; filters cannot be removed from the front of these units.
(1) Pipe termination side.
(2
) Opposite side to pipe terminations, including when electrical connections are present.
(3) Below floor option shown. Please contact Airedale for detailed clearance requirements for floor stand options.
A
B
C
D
SmartCool™
Precision Air Conditioning
Ins
ta
lla
tio
n