25
TM SmartCool One 5057724 v1.0_08_2022
2. It is possible to lift from the front or rear, close to the floor stand legs if a forklift is to be used.
3. The floor stand shall be provided with a roll of compressible foam tape to prevent air bypass during operation. The
tape shall be applied to the top face of the floor stand to sufficiently prevent air bypass once the unit has been
installed on top of the floor stand.
4. The unit shall be lifted off the shipping pallet using appropriate lifting equipment, such as skoots and lowered onto
the floor stand in it’s final position. For above floor stand applications or when using a forklift to manoeuvre the unit,
skoots should be used to lift the unit off the pallet, the pallet removed and then the skoots can lower the unit onto
the forks. In some cases the floor stand gland plate may need to be removed during this step to avoid clashing with
the lifting forks.
IF FORKLIFT IS USED ENSURE
THE FORKS FALL AS CLOSE AS
POSSIBLE TO THE CROSS RAILS
FOR STRENGTH
IF FORKLIFT IS USED ENSURE
THE FORKS FALL AS CLOSE AS
POSSIBLE TO THE CROSS RAILS
FOR STRENGTH
Precision Air Conditioning
SmartCool™
Ins
ta
lla
tio
n