Minimum Unit Ceiling Clearances For Airflow
Units Forward and 1 Side Forward and 2 Sides
All Faces
(1)
(2)
(3)
SO09 Standard Height
mm
300
200
150
in
11.8
7.9
5.9
SO12 Standard Height
mm
380
270
190
in
15.0
10.6
7.5
SO15 Standard Height
mm
440
330
220
in
17.3
13.0
8.7
SO18 Standard Height
mm
470
350
240
in
18.5
13.8
9.4
SO22 Standard Height
mm
520
410
260
in
20.5
16.1
10.2
SO25 Standard Height
mm
550
440
280
in
21.7
17.3
11.0
SO31 Standard Height
mm
600
490
300
in
23.6
19.3
11.8
SO35 Standard Height
mm
630
520
320
in
24.8
20.5
12.6
SO09 Extended Height
mm
350
230
180
in
13.8
9.1
7.1
SO12 Extended Height
mm
450
310
230
in
17.7
12.2
9.1
SO15 Extended Height
mm
520
380
260
in
20.5
15.0
10.2
SO18 Extended Height
mm
550
410
280
in
21.7
16.1
11.0
SO22 Extended Height
mm
610
480
310
in
24.0
18.9
12.2
SO25 Extended Height
mm
650
520
330
in
25.6
20.5
13.0
SO31 Extended Height
mm
710
580
360
in
28.0
22.8
14.2
SO35 Extended Height
mm
740
610
370
in
29.1
24.0
14.6
SO30
mm
880
620
440
in
34.6
24.4
17.3
SO40
mm
1010
750
510
in
39.8
29.5
20.1
SO50
mm
1090
830
550
in
42.9
32.7
21.7
SO60
mm
1260
990
630
in
49.6
39.0
24.8
Minimum Unit Ceiling Clearances For Airflow
The minimum unit ceiling clearances shown below correspond to the installation environment of the unit in relation to
adjacent walls, units, ceilings and other obstructions. These clearances are the minimum required to ensure adequate
unit return airflow is maintained during operation.