TM SmartCool One 5057724 v1.0_08_2022

0.0

5.0

10.0

15.0

20.0

25.0

30.0

0.00

50.00

100.00

150.00

200.00

250.00

300.00

Pr

es

su

re

 D

ro

p (

ft.H

2

O)

Flowrate (gpm)

SO35 High Flow 60Hz Unit

SO35D022CHBSx-3

SO35D025CHBXx-3

SO35D024CHCSx-3

SO35D028CHCXx-3

SO35D025CHDSx-3

SO35D029CHDXx-3

0.0

5.0

10.0

15.0

20.0

25.0

30.0

0.00

50.00

100.00

150.00

200.00

250.00

Pr

es

su

re

 D

ro

p (

ft.H

2

O)

Flowrate (gpm)

SO31 High Flow 60Hz Unit

SO31D019CHBSx-3

SO31D022CHBXx-3

SO31D021CHCSx-3

SO31D024CHCXx-3

SO31D022CHDSx-3

SO31D026CHDXx-3

Waterside Pressure Drop

Coil only

38

SO31D019CHBSx-3

39

SO31D022CHBXx-3

40

SO31D021CHCSx-3

41

SO31D024CHCXx-3

42

SO31D022CHDSx-3

43

SO31D026CHDXx-3

SO31 High Flow 60Hz

44

SO35D022CHBSx-3

45

SO35D025CHBXx-3

46

SO35D024CHCSx-3

47

SO35D028CHCXx-3

48

SO35D025CHDSx-3

49

SO35D029CHDXx-3

SO35 High Flow 60Hz

38

43

42

41

39

40

49

44

48

47

45

46

SmartCool™

Precision Air Conditioning

Te

ch

ni

ca

l

Содержание SmartCool Airedale

Страница 1: ...EMS52086 FM00542 SmartCoolTM One Downflow Dedicated Chilled Water Technical Manual Original Instructions ...

Страница 2: ...contains live electrical and moving parts ISOLATE prior to maintenance or repair work Ensure electrical lock off procedures are carried out ALL work MUST be carried out by technically trained competent personnel The equipment contains live electrical and moving parts ISOLATE prior to maintenance or repair work Ensure electrical lock off procedures are carried out Ensure that there are no other pow...

Страница 3: ...9 1000 service airedale com Technical Support 44 0 113 239 1000 tech support airedale com Training Enquiries 44 0 113 239 1000 training airedale com For information visit us at our website www airedale com Airedale endeavours to ensure that the information in this document is correct and fairly stated but none of the statements are to be relied upon as a statement or representation of fact Airedal...

Страница 4: ... gallons SmartCool Precision Air Conditioning Introduction Health and Safety The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation commissioning and maintenance of this Airedale unit Safety The equipment has been designed and manufactured to meet international safety standards but...

Страница 5: ...s Environmental Policy It is our policy to Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements Train personnel in sound environmental practices Pursue opportunities to conserve resources prevent pollution and eliminate waste Manufacture products in a responsible manner with minimum impact on the environment Reduce our use of chemicals and mi...

Страница 6: ...e 50Hz 35 Wire Flow Guide 60Hz 37 Flood Detection 39 Unit to Unit Network Termination 40 Glycol 41 Technical Data 42 Interconnected Wiring 42 Operating Temperature Limits 44 Waterside Pressure Drop Low Flow 50Hz 45 Waterside Pressure Drop High Flow 50Hz 49 Waterside Pressure Drop Low Flow 60Hz 55 Waterside Pressure Drop High Flow 60Hz 59 Sound Measurement Method 65 Sound Data 50Hz 66 Sound Data 60...

Страница 7: ...he flexibility of this type of installation provides for multi circuit functionality Precision Air Conditioning System The air conditioning equipment is designed specifically for precision temperature control and humidity monitoring applications It automatically monitors and controls cooling and filtering functions for the conditioned space The system is built to the highest quality engineering an...

Страница 8: ... v1 0_08_2022 System Configurations Floor Height Floor Stand Isolator Unit Control Display Air Filters Cooling Coil Fans Control Panel Example shown is SO09 with open floor stand SmartCool Precision Air Conditioning Introduction ...

Страница 9: ...8_2022 System Configurations Floor Height Floor Stand Isolator Unit Control Display Air Filters Cooling Coil Fans Control Panel Example shown is SO31 with open floor stand Control Valve Precision Air Conditioning SmartCool Introduction ...

Страница 10: ...8_2022 System Configurations Floor Height Floor Stand Isolator Unit Control Display Air Filters Cooling Coil Fans Control Panel Example shown is SO60 with open floor stand Control Valve SmartCool Precision Air Conditioning Introduction ...

Страница 11: ...test pressure is to no less than 20 Barg 290 1psi and the maximum operating pressure is no less than 10 Barg 145 0psi Low flow coil Typically 9 12K 16 2 21 6 F waterside ΔT cooling High flow coil Typically 6 9K 10 8 16 2 F waterside ΔT cooling 0 10 Volts DC 2 Port Chilled Water Regulating Valve For systems with variable speed pumps and water flow a 2 port control valve can be fitted The 2 port val...

Страница 12: ...ial hazard and catastrophic failure of the water circuit The pressure transducer monitors the pressure of the trapped liquid and opens the control valve once a setpoint is reached to relieve any built up pressure Once the pressure has returned to a safe level the control valve closes again Inlet Outlet Water Temperature Sensors NTC type probes are provided to monitor the chilled water inlet and ou...

Страница 13: ... Input Power Airflow EC Electronically Commutated Fan Speed Control Regulated VR Fan Speed Control Key ISO C 80 Filtration G4 equivalent Vertical pleated disposable panel filters in a rigid frame conforming to ISO C 80 are available as an option If these are selected the controller will provide an alarm following a pre set run time limit being exceeded Access and removal are from the front of the ...

Страница 14: ...L N voltage is 220V Single Power Supply Single power supply is a standard feature on the SmartCool One 0 and A supply voltage units have a door interlocked mains isolator as standard Door interlocked mains isolator is an optional feature for 3 supply voltage units Socomec ATyS t M 0 and A supply voltage ABB TruONE ATS 3 supply voltage Dual Power Supply ATS Dual power supply automatic transfer swit...

Страница 15: ...ases user safety Energy Manager Analysis of system energy consumption can be monitored via a dedicated LCD display Unit power information can be monitored via the controller allowing key information such as real power voltage current and power factor to be reviewed as well as providing additional alarm functionality such as phase loss Energy Manager 0 and A supply voltage Energy Manager 3 supply v...

Страница 16: ...monitoring and control features including a real time clock and industry standard communication port and network connections All the SmartCool products feature a 32 bit microprocessor offering significant calculation power and operation processing speed Also featured is the facility to adjust and display control settings by local operator for information and control Display Keypad The 4 3 touch sc...

Страница 17: ... Airedale Controls to ensure strategy compatibility NOTE Please specify preferred 4 digit Display Screen PIN at time of order NOTE Remote On Off Screened cable should be used for the Remote ON OFF to prevent negative effects to EMC levels Terminals for interlocking are provided Fire Shut Down Terminals for interlocking are provided to shut down the unit in the event of fire Fan Hours Run Log Reset...

Страница 18: ...d fan that is modulated to maintain a given set point Constant pressure control monitors the air pressure differential between two points In a typical application shown below the pressure under the raised floor red is compared to the room pressure blue The two pressure points positive and negative are routed back to an air differential pressure sensor inside the CRAH unit The value from the air pr...

Страница 19: ... of placing an order In some instances it may be preferred to maintain a standard floor stand height and install the unit and floor stand onto a plinth located in the floor void Plinths The SmartCool One range has a standard range of welded steel plinths as well as seismic plinths with increased structural support for seismic applications Please contact Airedale to discuss the range of options ava...

Страница 20: ... 78 0 89 8 35 0 23 5 SO18 mm 1800 1980 2280 890 571 2 in 70 9 78 0 89 8 35 0 23 5 SO22 mm 2200 1980 2280 890 571 3 in 86 6 78 0 89 8 35 0 23 5 SO25 mm 2500 1980 2280 890 571 3 in 98 4 78 0 89 8 35 0 23 5 SO31 mm 3100 1980 2280 890 571 4 in 122 1 78 0 89 8 35 0 23 5 SO35 mm 3500 1980 2280 890 571 4 in 137 1 78 0 89 8 35 0 23 5 Adjustable foot 25mm 1 not included Unit specific general arrangement dr...

Страница 21: ... 5 86 6 24 7 SO40 mm 4000 2400 2200 627 1 in 157 5 94 5 86 6 24 7 SO50 mm 5000 2400 2200 627 1 in 196 9 94 5 86 6 24 7 SO60 mm 6000 2400 2200 627 1 in 236 2 94 5 86 6 24 7 Adjustable foot 25mm 1 not included Unit specific general arrangement drawings are available upon request Please contact Airedale for more details A B D C Precision Air Conditioning SmartCool Installation ...

Страница 22: ... mm 1200 600 600 in 47 2 23 6 23 6 SO50 mm 1200 600 600 in 47 2 23 6 23 6 SO60 mm 1200 600 600 in 47 2 23 6 23 6 The minimum clearance requirements must be maintained around the units This is to ensure filters can be maintained from the front or side of the unit and that fans can be maintained from the front of the unit For below floor floor stand installations floor tile support posts must be rem...

Страница 23: ...12 2 9 1 SO15 Extended Height mm 520 380 260 in 20 5 15 0 10 2 SO18 Extended Height mm 550 410 280 in 21 7 16 1 11 0 SO22 Extended Height mm 610 480 310 in 24 0 18 9 12 2 SO25 Extended Height mm 650 520 330 in 25 6 20 5 13 0 SO31 Extended Height mm 710 580 360 in 28 0 22 8 14 2 SO35 Extended Height mm 740 610 370 in 29 1 24 0 14 6 SO30 mm 880 620 440 in 34 6 24 4 17 3 SO40 mm 1010 750 510 in 39 8 ...

Страница 24: ...ropped it should immediately be checked for damage Packed Dimensions Single slab units may be shipped mounted on a wooden pallet and covered with polythene The pallet shall be mechanically fixed to the unit for transportation only The packaging adds 50mm 2 to the length and width of the unit and 160mm 6 3 to it s height Please contact Airedale for this option WIDTH 50mm 2in DEPTH 50mm 2in HEIGHT 1...

Страница 25: ...en installed on top of the floor stand 4 The unit shall be lifted off the shipping pallet using appropriate lifting equipment such as skoots and lowered onto the floor stand in it s final position For above floor stand applications or when using a forklift to manoeuvre the unit skoots should be used to lift the unit off the pallet the pallet removed and then the skoots can lower the unit onto the ...

Страница 26: ...nce forks are removed 5 The unit and floor stand shall be fastened together using M6 fixings this is most important in seismic applications 6 The metal body of the floor stand should be bonded back to the main unit ground by means of a ground wire and lug connection local to the floor stand gland plate This is specific to the 60Hz units only 7 Check that external panel fixings are tightened to a t...

Страница 27: ...4 Point Lifting Floor Stand 2292mm 90 2in Unit 4 Point Lift A mm in SO30 2477 97 5 SO40 2950 116 4 Point Lifting Unit Unit 4 Point Lift A mm in SO30 2389 94 1 SO40 3389 133 4 2152 8mm 84 76 in Precision Air Conditioning SmartCool Installation ...

Страница 28: ...in 2292mm 90 2in Unit 8 Point Lift A B mm in mm in SO50 2340 92 1600 63 SO60 3380 133 1600 63 8 Point Lifting Floor Stand Unit 8 Point Lift A B mm in mm in SO50 2557 100 7 1705 67 1 SO60 3007 118 4 2256 88 8 2152 8mm 84 76 in SmartCool Precision Air Conditioning Installation ...

Страница 29: ... The requirements shall include but are not limited to type embedment depth edge spacing anchor spacing concrete strength and wall bracing The Structural Engineer must also approve that the floors and concrete pads are seismically designed to withstand the anchor loads of the equipment Unit connections for wiring ductwork and pipework should be considered where applicable and approved by the Struc...

Страница 30: ...USTOMER ORDER No SALES No MANUF No 2 WAY VALVE OPEN POSITION 2 WAY VALVE CLOSED POSITION UNIT DESCRIPTION INLET LEG A OUTLET LEG B BYPASS LEG D MANIFOLDS C WTS PDZAL M M M PT PT ALL DIMENSIONS ARE IN mm U O S THIS DRAWING IS THE PROPERTY OF THE AIREDALE GROUP OF COMPANIES IT MUST DRAWN TITLE ORIGINAL SCALE NAME DATE 11 01 21 CD SO09 35D SMARTCOOL ONE PIPEWORK SCHEMATIC CUSTOMER ORDER No SALES No M...

Страница 31: ...AY VALVE OPEN POSITION 2 WAY VALVE CLOSED POSITION UNIT DESCRIPTION INLET LEG A OUTLET LEG B BYPASS LEG F STEEL MANIFOLDS C STEEL COPPER LEG D COIL MANIFOLDS E WTS PDZAL M M PT PT ALL DIMENSIONS ARE IN mm U O S TITLE ORIGINAL SCALE NAME DATE SO30 60D SMARTCOOL ONE PIPEWORK SCHEMATIC CUSTOMER ORDER No SALES No 2 WAY VALVE OPEN POSITION 2 WAY VALVE CLOSED POSITION UNIT DESCRIPTION INLET LEG A OUTLET...

Страница 32: ...e and a PICV in the same system These two components will work against each other and will affect performance UNIT RETURN UNIT SUPPLY CUSTOMER CONNECTIONS IV IV IV IV Key Pressure Test Point Automatic Air Vent Drain Off Cock Valve Isolating Valve Flow Measuring Device Flanged Connections Pump Strainer UNIT RETURN UNIT SUPPLY CUSTOMER CONNECTIONS IV IV IV IV UNIT RETURN UNIT SUPPLY CUSTOMER CONNECT...

Страница 33: ...oming Services SO30 50 SO60 A B C D E F mm in mm in mm in mm in mm in mm in SO30 50 2200 86 6 2400 94 5 1255 49 4 945 37 2 443 17 4 703 5 27 7 SO60 2200 86 6 2400 94 5 1255 49 4 945 37 2 444 9 17 5 A A B B C C D D E F E Image shows LHS terminations RHS terminations are mirrored Image shows RHS terminations LHS terminations are mirrored Precision Air Conditioning SmartCool Installation ...

Страница 34: ...oth LHS RHS for both standard and extended height units SO09 35 allows electrical terminations to be on the same or opposite side as the pipe terminations Front of unit A B C D mm 50 422 6 352 6 252 6 in 1 97 16 64 13 88 9 94 A B C D A B C D mm 85 530 445 305 in 3 35 20 87 17 42 12 01 A B C D A B C D SmartCool Precision Air Conditioning Installation ...

Страница 35: ...y The wire should be securely fastened to the frame with the use of cable ties or other means of fixing appropriate to the application For unit specific wire paths please contact Airedale LHS Pipe Termination Single Power Supply LHS Pipe Termination Dual Power Supply Both left and right hand side wiring entry is available on units with LHS pipework termination Precision Air Conditioning SmartCool ...

Страница 36: ...ation Dual Power Supply General wire path shown only The wire should be securely fastened to the frame with the use of cable ties or other means of fixing appropriate to the application For unit specific wire paths please contact Airedale Both left and right hand side wiring entry is available on units with RHS pipework termination SmartCool Precision Air Conditioning Installation ...

Страница 37: ...tion Dual Power Supply LHS Pipe Termination Dual Power Supply Disconnect Switches General wire path shown only The wire should be securely fastened to the frame with the use of cable ties or other means of fixing appropriate to the application For unit specific wire paths please contact Airedale Both left and right hand side wiring entry is available on units with LHS pipework termination Precisio...

Страница 38: ...pe Termination Dual Power Supply Disconnect Switches General wire path shown only The wire should be securely fastened to the frame with the use of cable ties or other means of fixing appropriate to the application For unit specific wire paths please contact Airedale Both left and right hand side wiring entry is available on units with RHS pipework termination SmartCool Precision Air Conditioning ...

Страница 39: ...f adhesive clips may interfere with the flood detection capability or adversely affect the designed function The rope sensor should not be installed under piping or equipment that can condense liquid as the condensation could drip on the rope causing an alarm In the sub floor of a computer room the rope should be installed after the raised floor conduit and piping are installed and the sub floor c...

Страница 40: ...ided image with a column of water A minimum height difference must be ensured and can be calculated as shown The purpose of this is to prevent air bypassing the chilled water coil through the drain tube and to allow condensate to drain properly while the unit is running The p trap should be checked during service and maintenance visits and topped up to ensure the minimum height difference is prese...

Страница 41: ... 015 0 959 3 872 0 925 3 716 0 888 3 552 0 848 Density ρ kg m lb ft Water Glycol Temperature Ethylene Glycol Volume Freezing Point 0 0 C 32 F 10 4 C 24 8 F 20 9 C 15 8 F 30 15 C 5 F 40 23 C 9 4 F C ρ ρ ρ ρ ρ 20 68 998 62 3 1013 63 2 1030 64 3 1045 65 2 1060 66 2 25 77 997 62 2 1012 63 2 1028 64 2 1043 65 1 1058 66 0 30 86 996 62 2 1010 63 1 1026 64 1 1041 65 0 1055 65 9 35 95 994 62 1 1008 62 9 10...

Страница 42: ... Floor Stand Fan 2 Power Connector X21 224 225 PE Fan 3 SO22 SO60 226 Unit to Floor Stand Fan 3 Power Connector X22 227 228 PE Fan 4 SO30 SO60 229 Unit to Floor Stand Fan 4 Power Connector X23 230 231 PE Fan 5 SO30 SO60 A Frame Only 232 Unit to Floor Stand Fan 5 Power Connector X24 233 234 PE Fan 6 SO30 SO60 A Frame Only 235 Unit to Floor Stand Fan 6 Power Connector X25 236 237 PE Fan 7 SO40 SO60 ...

Страница 43: ... Rx Tx Network In FBUS2 Rx Tx GND Standard Rx Tx Network Out FBUS2 Rx Tx GND Standard 502 Remote On Off 522 Standard 560 Non Critical Alarm N O 561 Non Critical Alarm Common Standard 560 Critical Alarm N O 561 Critical Alarm Common 562 Critical Alarm N C Standard 502 Fire Smoke Detect 583 Standard 609 Flood Detection Tape Probe 610 Standard 812 Supply Air Temperature 854 Option 500 Supply Air Temp...

Страница 44: ...st be controlled by the customer to ensure a non latent application Minimum Design Maximum C F C F C F Return Air Temperature 28 82 4 36 75 2 45 113 0 Return Air Relative Humidity 9 4 22 6 32 7 Inlet Water Temperature 20 68 28 82 4 36 96 8 Temperature Difference K R 6K 10 8 R 8K 14 4 R 12K 21 6 R Storage Temperature Please contact Airedale SmartCool Precision Air Conditioning Technical ...

Страница 45: ...0 1 60 1 80 2 00 Pressure Drop kPa Flowrate l s SO09 Low Flow 50Hz Unit SO09D004CLBSx 0 A SO09D004CLBXx 0 A SO09D004CLCSx 0 A SO09D005CLCXx 0 A SO09D005CLDSx 0 A SO09D005CLDXx 0 A Waterside Pressure Drop Coil only 1 6 5 4 3 2 1 SO09D004CLBSx 0 A 2 SO09D004CLBXx 0 A 3 SO09D004CLCSx 0 A 4 SO09D005CLCXx 0 A 5 SO09D005CLDSx 0 A 6 SO09D005CLDXx 0 A 7 SO12D006CLBSx 0 A 8 SO12D006CLBXx 0 A 9 SO12D006CLCS...

Страница 46: ...4 00 4 50 Pressure Drop kPa Flowrate l s SO15 Low Flow 50Hz Unit SO15D007CLBSx 0 A SO15D009CLBXx 0 A SO15D008CLCSx 0 A SO15D010CLCXx 0 A SO15D009CLDSx 0 A SO15D010CLDXx 0 A Waterside Pressure Drop Coil only 13 SO15D007CLBSx 0 A 14 SO15D009CLBXx 0 A 15 SO15D008CLCSx 0 A 16 SO15D010CLCXx 0 A 17 SO15D009CLDSx 0 A 18 SO15D010CLDXx 0 A 19 SO18D009CLBSx 0 A 20 SO18D010CLBXx 0 A 21 SO18D010CLCSx 0 A 22 S...

Страница 47: ...re Drop kPa Flowrate l s SO22 Low Flow 50Hz Unit SO22D011CLBSx 0 A SO22D013CLBXx 0 A SO22D013CLCSx 0 A SO22D015CLCXx 0 A SO22D014CLDSx 0 A SO22D016CLDXx 0 A Waterside Pressure Drop Coil only 25 SO22D011CLBSx 0 A 26 SO22D013CLBXx 0 A 27 SO22D013CLCSx 0 A 28 SO22D015CLCXx 0 A 29 SO22D014CLDSx 0 A 30 SO22D016CLDXx 0 A 31 SO25D013CLBSx 0 A 32 SO25D015CLBXx 0 A 33 SO25D015CLCSx 0 A 34 SO25D017CLCXx 0 A...

Страница 48: ...essure Drop kPa Flowrate l s SO31 Low Flow 50Hz Unit SO31D017CLBSx 0 A SO31D020CLBXx 0 A SO31D019CLCSx 0 A SO31D022CLCXx 0 A SO31D020CLDSx 0 A SO31D024CLDXx 0 A Waterside Pressure Drop Coil only 37 SO31D017CLBSx 0 A 38 SO31D020CLBXx 0 A 39 SO31D019CLCSx 0 A 40 SO31D022CLCXx 0 A 41 SO31D020CLDSx 0 A 42 SO31D024CLDXx 0 A 43 SO35D019CLBSx 0 A 44 SO35D022CLBXx 0 A 45 SO35D021CLCSx 0 A 46 SO35D025CLCXx...

Страница 49: ... 1 00 1 50 2 00 2 50 3 00 Pressure Drop kPa Flowrate l s SO09 High Flow 50Hz Unit SO09D004CHBSx 0 A SO09D005CHBXx 0 A SO09D004CHCSx 0 A SO09D005CHCXx 0 A SO09D005CHDSx 0 A SO09D005CHDXx 0 A Waterside Pressure Drop Coil only 1 SO09D004CHBSx 0 A 2 SO09D005CHBXx 0 A 3 SO09D004CHCSx 0 A 4 SO09D005CHCXx 0 A 5 SO09D005CHDSx 0 A 6 SO09D005CHDXx 0 A 7 SO12D006CHBSx 0 A 8 SO12D007CHBXx 0 A 9 SO12D006CHCSx ...

Страница 50: ...0 6 00 7 00 Pressure Drop kPa Flowrate l s SO15 High Flow 50Hz Unit SO15D008CHBSx 0 A SO15D009CHBXx 0 A SO15D009CHCSx 0 A SO15D010CHCXx 0 A SO15D009CHDSx 0 A SO15D011CHDXx 0 A Waterside Pressure Drop Coil only 13 SO15D008CHBSx 0 A 14 SO15D009CHBXx 0 A 15 SO15D009CHCSx 0 A 16 SO15D010CHCXx 0 A 17 SO15D009CHDSx 0 A 18 SO15D011CHDXx 0 A 19 SO18D009CHBSx 0 A 20 SO18D011CHBXx 0 A 21 SO18D010CHCSx 0 A 2...

Страница 51: ...12 00 Pressure Drop kPa Flowrate l s SO22 High Flow 50Hz Unit SO22D012CHBSx 0 A SO22D014CHBXx 0 A SO22D013CHCSx 0 A SO22D015CHCXx 0 A SO22D014CHDSx 0 A SO22D016CHDXx 0 A Waterside Pressure Drop Coil only 25 SO22D012CHBSx 0 A 26 SO22D014CHBXx 0 A 27 SO22D013CHCSx 0 A 28 SO22D015CHCXx 0 A 29 SO22D014CHDSx 0 A 30 SO22D016CHDXx 0 A 31 SO25D014CHBSx 0 A 32 SO25D016CHBXx 0 A 33 SO25D015CHCSx 0 A 34 SO25...

Страница 52: ...00 12 00 14 00 16 00 Pressure Drop kPa Flowrate l s SO31 High Flow 50Hz Unit SO31D018CHBSx 0 A SO31D021CHBXx 0 A SO31D019CHCSx 0 A SO31D023CHCXx 0 A SO31D021CHDSx 0 A SO31D025CHDXx 0 A Waterside Pressure Drop Coil only 37 SO31D018CHBSx 0 A 38 SO31D021CHBXx 0 A 39 SO31D019CHCSx 0 A 40 SO31D023CHCXx 0 A 41 SO31D021CHDSx 0 A 42 SO31D025CHDXx 0 A 43 SO35D020CHBSx 0 A 44 SO35D024CHBXx 0 A 45 SO35D022CH...

Страница 53: ...SO40D059CLDSx 0 A SO40D061CHDSx 0 A 0 0 20 0 40 0 60 0 80 0 100 0 120 0 0 00 2 00 4 00 6 00 8 00 10 00 12 00 Pressure Drop kPa Flowrate l s SO30 50Hz Unit SO30D043CLDSx 0 A SO30D045CHDSx 0 A Waterside Pressure Drop Coil only 1 SO30D043CLDSx 0 A 2 SO30D045CHDXx 0 A 3 SO40D059CLDSx 0 A 4 SO40D061CHDXx 0 A 1 2 SO30 50Hz SO40 50Hz 3 4 Precision Air Conditioning SmartCool Technical ...

Страница 54: ...D101CHDSx 0 A 0 0 20 0 40 0 60 0 80 0 100 0 120 0 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 16 00 18 00 20 00 Pressure Drop kPa Flowrate l s SO50 50Hz Unit SO50D074CLDSx 0 A SO50D077CHDSx 0 A Waterside Pressure Drop Coil only 5 SO50D074CLDSx 0 A 6 SO50D077CHDXx 0 A 7 SO60D097CLDSx 0 A 8 SO60D101CHDXx 0 A 5 6 SO50 50Hz SO60 50Hz 7 8 SmartCool Precision Air Conditioning Technical ...

Страница 55: ...0 00 15 00 20 00 25 00 30 00 Pressure Drop ft H 2 O Flowrate gpm SO09 Low Flow 60Hz Unit SO09D004CLBSx 3 SO09D005CLBXx 3 SO09D004CLCSx 3 SO09D005CLCXx 3 SO09D005CLDSx 3 SO09D006CLDXx 3 Waterside Pressure Drop Coil only 1 SO09D004CLBSx 3 2 SO09D005CLBXx 3 3 SO09D004CLCSx 3 4 SO09D005CLCXx 3 5 SO09D005CLDSx 3 6 SO09D006CLDXx 3 1 6 4 5 2 3 SO09 Low Flow 60Hz 7 SO12D006CLBSx 3 8 SO12D007CLBXx 3 9 SO12...

Страница 56: ... 40 00 50 00 60 00 70 00 Pressure Drop ft H 2 O Flowrate gpm SO15 Low Flow 60Hz Unit SO15D008CLBSx 3 SO15D009CLBXx 3 SO15D009CLCSx 3 SO15D010CLCXx 3 SO15D009CLDSx 3 SO15D011CLDXx 3 Waterside Pressure Drop Coil only 13 SO15D008CLBSx 3 14 SO15D009CLBXx 3 15 SO15D009CLCSx 3 16 SO15D010CLCXx 3 17 SO15D009CLDSx 3 18 SO15D011CLDXx 3 SO15 Low Flow 60Hz 19 SO18D010CLBSx 3 20 SO18D011CLBXx 3 21 SO18D010CLC...

Страница 57: ...0 00 70 00 80 00 90 00 100 00 Pressure Drop ft H 2 O Flowrate gpm SO22 Low Flow 60Hz Unit SO22D012CLBSx 3 SO22D014CLBXx 3 SO22D013CLCSx 3 SO22D016CLCXx 3 SO22D014CLDSx 3 SO22D017CLDXx 3 Waterside Pressure Drop Coil only 26 SO22D012CLBSx 3 27 SO22D014CLBXx 3 28 SO22D013CLCSx 3 29 SO22D016CLCXx 3 30 SO22D014CLDSx 3 31 SO22D017CLDXx 3 26 31 29 30 27 28 SO22 Low Flow 60Hz 32 SO25D014CLBSx 3 33 SO25D01...

Страница 58: ...60 00 80 00 100 00 120 00 140 00 Pressure Drop ft H 2 O Flowrate gpm SO31 Low Flow 60Hz Unit SO31D018CLBSx 3 SO31D021CLBXx 3 SO31D020CLCSx 3 SO31D023CLCXx 3 SO31D022CLDSx 3 SO31D025CLDXx 3 Waterside Pressure Drop Coil only 38 SO31D018CLBSx 3 39 SO31D021CLBXx 3 40 SO31D020CLCSx 3 41 SO31D023CLCXx 3 42 SO31D022CLDSx 3 43 SO31D025CLDXx 3 SO31 Low Flow 60Hz 44 SO35D021CLBSx 3 45 SO35D024CLBXx 3 46 SO3...

Страница 59: ...5 00 30 00 35 00 40 00 45 00 50 00 Pressure Drop ft H 2 O Flowrate gpm SO09 High Flow 60Hz Unit SO09D004CHBSx 3 SO09D005CHBXx 3 SO09D005CHCSx 3 SO09D005CHCXx 3 SO09D005CHDSx 3 SO09D006CHDXx 3 Waterside Pressure Drop Coil only 1 SO09D004CHBSx 3 2 SO09D005CHBXx 3 3 SO09D005CHCSx 3 4 SO09D005CHCXx 3 5 SO09D005CHDSx 3 6 SO09D006CHDXx 3 1 6 4 5 2 3 SO09 High Flow 60Hz 7 SO12D006CHBSx 3 8 SO12D007CHBXx ...

Страница 60: ... 00 120 00 Pressure Drop ft H 2 O Flowrate gpm SO15 High Flow 60Hz Unit SO15D008CHBSx 3 SO15D010CHBXx 3 SO15D009CHCSx 3 SO15D011CHCXx 3 SO15D010CHDSx 3 SO15D011CHDXx 3 Waterside Pressure Drop Coil only 13 SO15D008CHBSx 3 14 SO15D010CHBXx 3 15 SO15D009CHCSx 3 16 SO15D011CHCXx 3 17 SO15D010CHDSx 3 18 SO15D011CHDXx 3 SO15 High Flow 60Hz 19 SO18D010CHBSx 3 20 SO18D012CHBXx 3 21 SO18D011CHCSx 3 22 SO18...

Страница 61: ... 00 120 00 140 00 160 00 180 00 Pressure Drop ft H 2 O Flowrate gpm SO22 High Flow 60Hz Unit SO22D013CHBSx 3 SO22D015CHBXx 3 SO22D014CHCSx 3 SO22D016CHCXx 3 SO22D015CHDSx 3 SO22D017CHDXx 3 Waterside Pressure Drop Coil only 26 SO22D013CHBSx 3 27 SO22D015CHBXx 3 28 SO22D014CHCSx 3 29 SO22D016CHCXx 3 30 SO22D015CHDSx 3 31 SO22D017CHDXx 3 26 31 29 30 27 28 SO22 High Flow 60Hz 32 SO25D015CHBSx 3 33 SO2...

Страница 62: ...0 00 Pressure Drop ft H 2 O Flowrate gpm SO31 High Flow 60Hz Unit SO31D019CHBSx 3 SO31D022CHBXx 3 SO31D021CHCSx 3 SO31D024CHCXx 3 SO31D022CHDSx 3 SO31D026CHDXx 3 Waterside Pressure Drop Coil only 38 SO31D019CHBSx 3 39 SO31D022CHBXx 3 40 SO31D021CHCSx 3 41 SO31D024CHCXx 3 42 SO31D022CHDSx 3 43 SO31D026CHDXx 3 SO31 High Flow 60Hz 44 SO35D022CHBSx 3 45 SO35D025CHBXx 3 46 SO35D024CHCSx 3 47 SO35D028CH...

Страница 63: ...9CLDSx 3 SO40D061CHDSx 3 0 0 5 0 10 0 15 0 20 0 25 0 30 0 35 0 0 00 20 00 40 00 60 00 80 00 100 00 120 00 140 00 160 00 180 00 Pressure Drop ft H 2 O Flowrate gpm SO30 60Hz Unit SO30D043CLDSx 3 SO30D044CHDSx 3 Waterside Pressure Drop Coil only 1 SO30D043CLDSx 3 2 SO30D044CHDXx 3 3 SO40D059CLDSx 3 4 SO40D061CHDXx 3 1 2 SO30 60Hz SO40 60Hz 3 4 Precision Air Conditioning SmartCool Technical ...

Страница 64: ...it SO60D096CLDSx 3 SO60D100CHDSx 3 0 0 5 0 10 0 15 0 20 0 25 0 30 0 35 0 0 00 50 00 100 00 150 00 200 00 250 00 300 00 350 00 Pressure Drop ft H 2 O Flowrate gpm SO50 60Hz Unit SO50D074CLDSx 3 SO50D076CHDSx 3 Waterside Pressure Drop Coil only 5 SO50D074CLDSx 3 6 SO50D076CHDXx 3 7 SO60D096CLDSx 3 8 SO60D100CHDXx 3 5 6 SO50 60Hz SO60 60Hz 78 SmartCool Precision Air Conditioning Technical ...

Страница 65: ...e Field For comparison the semi hemispherical figures can typically be reduced by 3dB to provide free field conditions The sound data quoted is based on the unit having a ducted return air ducted or underfloor discharge air and standard backward curved fan and EC motors fitted refer to illustration below NOTE Case breakout sound data is therefore independent of the discharge air and return air sou...

Страница 66: ... A Discharge Air 92 91 99 93 89 87 81 75 67 Return Air 83 85 98 82 75 69 67 61 48 Case Breakout 80 82 92 81 77 73 68 60 56 Sound Pressure 3m 9 8ft 63 64 74 63 59 56 51 42 38 SO09xxxCxBXx 0 A Discharge Air 88 84 85 83 84 84 78 80 63 Return Air 74 78 84 73 70 67 63 65 44 Case Breakout 75 74 78 71 72 71 65 64 52 Sound Pressure 3m 9 8ft 57 57 60 54 54 53 47 47 34 SO12xxxCxBXx 0 A Discharge Air 91 90 9...

Страница 67: ...A Discharge Air 88 84 85 84 83 84 78 78 63 Return Air 74 78 83 73 69 67 64 64 45 Case Breakout 75 74 77 72 71 71 65 63 52 Sound Pressure 3m 9 8ft 57 57 60 54 54 53 48 45 35 SO12xxxCxCXx 0 A Discharge Air 91 90 97 93 88 86 82 76 68 Return Air 82 84 96 82 74 68 68 62 50 Case Breakout 79 80 90 81 76 72 69 61 57 Sound Pressure 3m 9 8ft 62 63 72 63 58 54 52 43 40 SO15xxxCxCXx 0 A Discharge Air 91 87 88...

Страница 68: ...1 76 73 69 61 58 Sound Pressure 3m 9 8ft 62 63 73 63 59 55 51 43 41 SO15xxxCxDXx 0 A Discharge Air 91 87 88 88 87 88 82 81 67 Return Air 77 81 87 77 73 70 68 67 49 Case Breakout 78 78 81 76 75 74 69 66 56 Sound Pressure 3m 9 8ft 61 60 63 58 57 57 52 48 39 SO18xxxCxDXx 0 A Discharge Air 91 90 99 92 88 86 79 75 67 Return Air 82 84 97 81 74 69 65 60 48 Case Breakout 80 80 91 80 76 73 66 59 56 Sound P...

Страница 69: ...3 Discharge Air 93 92 100 93 90 88 81 76 68 Return Air 84 86 99 83 76 70 67 61 49 Case Breakout 81 82 93 81 78 74 68 60 57 Sound Pressure 3m 9 8ft 64 64 75 64 60 56 51 43 39 SO09xxxCxBXx 3 Discharge Air 88 84 85 84 84 85 79 79 63 Return Air 74 78 84 73 70 67 64 64 45 Case Breakout 75 74 78 72 72 71 66 63 52 Sound Pressure 3m 9 8ft 57 57 60 54 54 53 48 46 35 SO12xxxCxBXx 3 Discharge Air 91 90 97 93...

Страница 70: ... 3 Discharge Air 88 84 85 84 83 84 79 77 64 Return Air 74 78 84 74 69 67 65 63 46 Case Breakout 75 74 78 72 71 71 66 62 53 Sound Pressure 3m 9 8ft 57 57 60 55 54 53 49 44 36 SO12xxxCxCXx 3 Discharge Air 92 90 98 93 89 86 82 77 70 Return Air 83 84 97 83 75 69 68 62 51 Case Breakout 80 80 91 81 77 73 69 61 59 Sound Pressure 3m 9 8ft 63 63 73 64 59 55 52 44 41 SO15xxxCxCXx 3 Discharge Air 91 87 89 88...

Страница 71: ... 81 77 73 69 61 59 Sound Pressure 3m 9 8ft 63 63 74 64 60 56 51 44 41 SO15xxxCxDXx 3 Discharge Air 92 88 89 88 87 88 83 81 69 Return Air 78 82 87 78 73 71 69 66 50 Case Breakout 79 78 81 76 75 75 70 65 58 Sound Pressure 3m 9 8ft 61 61 64 59 58 57 53 48 40 SO18xxxCxDXx 3 Discharge Air 92 90 99 92 89 87 80 76 68 Return Air 83 84 98 81 75 69 65 61 50 Case Breakout 80 81 92 80 77 73 67 60 57 Sound Pre...

Страница 72: ...Flow Rate l s 0 88 1 32 1 77 2 11 2 69 3 13 4 00 4 60 1 03 1 55 2 07 2 46 Pressure Drop 3 kPa 99 4 94 4 87 6 94 2 79 2 88 5 88 7 80 8 102 1 98 6 90 2 96 3 Fan Motor Centrifugal Quantity x Motor Size kW 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 Speed 25Pa Maximum ESP rpm 1246 1780 1140 1420 1270 1780 1020 1420 1323 1780 1026 1420 101...

Страница 73: ...r Flow Rate l s 3 15 3 65 4 70 5 38 0 98 1 47 1 97 2 34 3 00 3 48 4 47 5 12 Pressure Drop 3 kPa 91 2 89 7 83 4 85 5 99 8 96 4 92 8 94 0 89 5 89 3 79 4 85 4 Fan Motor Centrifugal Quantity x Motor Size kW 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 Speed 25Pa Maximum ESP rpm 1490 1780 1149 1420 1134 1420 1216 1420 1312 1780 1190 1420 13...

Страница 74: ...ater Flow Rate l s 1 15 1 72 2 30 2 74 3 50 4 06 5 22 5 97 1 08 1 61 2 15 2 56 Pressure Drop 3 kPa 89 3 81 1 95 1 81 3 89 2 90 0 84 4 84 4 82 5 96 4 93 9 91 4 Fan Motor Centrifugal Quantity x Motor Size kW 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 Speed 25Pa Maximum ESP rpm 1450 1780 1329 1420 1482 1780 1189 1420 1544 1780 1198 1420...

Страница 75: ... 215 1 Water Flow Rate l s 3 28 3 81 4 90 5 60 1 25 1 86 2 50 2 99 3 82 4 45 5 70 6 50 Pressure Drop 3 kPa 91 7 87 6 83 7 84 6 93 3 90 3 88 8 92 5 91 6 78 6 85 8 84 3 Fan Motor Centrifugal Quantity x Motor Size kW 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 Speed 25Pa Maximum ESP rpm 1435 1780 1133 1420 1122 1420 1180 1420 1500 1780 1...

Страница 76: ...0 9 Water Flow Rate l s 10 28 14 10 17 67 23 08 1 16 1 75 2 32 2 77 3 54 4 10 5 27 6 03 Pressure Drop 3 kPa 62 3 78 7 64 5 74 6 58 6 55 3 47 1 52 1 48 7 47 1 56 1 42 1 Fan Motor Centrifugal Quantity x Motor Size kW 6 x 3 70 8 x 3 70 10 x 3 70 14 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 Speed 25Pa Maximum ESP rpm 1417 1420 1418 1420 1418 1420 1418 1420 1247 178...

Страница 77: ... Flow Rate l s 1 36 2 04 2 71 3 23 4 12 4 78 6 15 7 03 1 28 1 92 2 55 3 05 Pressure Drop 3 kPa 69 0 60 5 52 3 59 1 47 4 52 8 42 7 47 0 64 5 58 8 49 9 56 1 Fan Motor Centrifugal Quantity x Motor Size kW 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 Speed 25Pa Maximum ESP rpm 1392 1780 1287 1420 1426 1780 1139 1420 1490 1780 1149 1420 113...

Страница 78: ...ater Flow Rate l s 3 89 4 51 5 80 6 65 1 50 2 24 2 98 3 56 4 53 5 25 6 77 7 79 Pressure Drop 3 kPa 50 9 49 3 56 6 46 8 58 3 51 8 55 3 47 6 49 7 56 7 45 3 56 5 Fan Motor Centrifugal Quantity x Motor Size kW 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 Speed 25Pa Maximum ESP rpm 1384 1780 1083 1420 1073 1420 1134 1420 1450 1780 1329 1420...

Страница 79: ...01 3 Water Flow Rate l s 1 39 2 08 2 77 3 31 4 22 4 93 6 30 7 21 1 62 2 42 3 22 3 85 Pressure Drop 3 kPa 70 7 61 2 52 4 59 7 46 6 52 0 42 5 47 1 53 5 47 6 59 3 44 2 Fan Motor Centrifugal Quantity x Motor Size kW 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 1 x 3 35 1 x 3 70 2 x 3 35 2 x 3 70 Speed 25Pa Maximum ESP rpm 1375 1780 1238 1420 1391 1780 1128 1420 1435 1780 113...

Страница 80: ... 91 5 73 7 32 8 39 13 30 18 20 22 85 30 02 Pressure Drop 3 kPa 53 1 43 4 47 7 56 3 69 4 60 2 55 5 83 4 Fan Motor Centrifugal Quantity x Motor Size kW 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 6 x 3 70 8 x 3 70 10 x 3 70 14 x 3 70 Speed 25Pa Maximum ESP rpm 1581 1780 1233 1420 1218 1420 1293 1420 1417 1420 1418 1420 1418 1420 1418 1420 Maximum ESP Pa 292 295 310 219 27 27 26 26 Nominal Airflow 1 m s 10 3...

Страница 81: ...0 19 4 22 7 18 9 18 6 Dimensions Depth mm 890 890 890 890 890 890 890 890 890 890 890 890 Height mm 1980 1980 1980 1980 1980 1980 1980 1980 2280 2280 2280 2280 Width mm 900 1200 1500 1800 2200 2500 3100 3500 900 1200 1500 1800 Mass Machine Operating kg 260 281 314 346 364 406 410 459 478 542 526 600 636 734 696 808 289 315 351 389 409 461 483 543 Unit Water Volume l 21 3 31 8 42 1 49 1 64 1 73 7 9...

Страница 82: ...17 6 17 7 17 1 19 0 Dimensions Depth mm 890 890 890 890 890 890 890 890 890 890 890 890 Height mm 2280 2280 2280 2280 1980 1980 1980 1980 1980 1980 1980 1980 Width mm 2200 2500 3100 3500 900 1200 1500 1800 2200 2500 3100 3500 Mass Machine Operating kg 536 610 591 676 717 829 783 912 275 304 336 379 392 446 447 514 521 603 575 670 700 826 768 911 Unit Water Volume l 73 8 84 7 112 5 128 6 29 0 42 9 ...

Страница 83: ...19 0 22 5 18 7 18 9 Dimensions Depth mm 890 890 890 890 890 890 890 890 1050 1050 1050 1050 Height mm 2280 2280 2280 2280 2280 2280 2280 2280 1980 1980 1980 1980 Width mm 900 1200 1500 1800 2200 2500 3100 3500 900 1200 1500 1800 Mass Machine Operating kg 307 340 376 426 442 508 522 599 586 682 656 771 790 935 874 1048 310 348 378 431 446 518 504 588 Unit Water Volume l 33 4 49 3 66 2 77 2 95 5 115...

Страница 84: ...4 19 7 21 7 Dimensions Depth mm 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 Height mm 1980 1980 1980 1980 2280 2280 2280 2280 2280 2280 2280 2280 Width mm 2200 2500 3100 3500 900 1200 1500 1800 2200 2500 3100 3500 Mass Machine Operating kg 590 693 667 792 800 965 879 1067 348 392 425 487 502 584 569 665 672 797 755 899 905 1093 996 1211 Unit Water Volume l 103 9 125 1 165 0 188 1 4...

Страница 85: ...7 7 17 1 19 0 Dimensions Depth mm 2200 2200 2200 2200 890 890 890 890 890 890 890 890 Height mm 2400 2400 2400 2400 1980 1980 1980 1980 1980 1980 1980 1980 Width mm 3000 4000 5000 6000 900 1200 1500 1800 2200 2500 3100 3500 Mass Machine Operating kg 1815 2289 2362 3004 2956 3771 3561 4589 261 284 316 350 368 413 414 466 479 543 533 612 637 735 716 837 Unit Water Volume l 474 7 641 6 815 3 1028 8 2...

Страница 86: ...6 19 1 22 7 18 6 18 9 Dimensions Depth mm 890 890 890 890 890 890 890 890 890 890 890 890 Height mm 2280 2280 2280 2280 2280 2280 2280 2280 1980 1980 1980 1980 Width mm 900 1200 1500 1800 2200 2500 3100 3500 900 1200 1500 1800 Mass Machine Operating kg 289 315 352 390 409 461 483 543 543 622 599 689 737 857 804 941 276 305 337 380 396 453 447 514 Unit Water Volume l 25 9 38 2 51 6 60 0 78 5 89 9 1...

Страница 87: ...0 2 19 9 19 3 21 6 Dimensions Depth mm 890 890 890 890 890 890 890 890 890 890 890 890 Height mm 1980 1980 1980 1980 2280 2280 2280 2280 2280 2280 2280 2280 Width mm 2200 2500 3100 3500 900 1200 1500 1800 2200 2500 3100 3500 Mass Machine Operating kg 522 604 583 683 705 839 788 941 307 341 376 426 442 508 522 599 593 693 657 772 810 962 888 1062 Unit Water Volume l 82 7 100 4 133 3 152 3 33 4 49 2...

Страница 88: ... 25 5 21 1 21 4 Dimensions Depth mm 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 Height mm 1980 1980 1980 1980 1980 1980 1980 1980 2280 2280 2280 2280 Width mm 900 1200 1500 1800 2200 2500 3100 3500 900 1200 1500 1800 Mass Machine Operating kg 309 345 379 432 446 518 504 588 597 705 668 793 814 979 894 1082 349 393 430 495 502 584 576 677 Unit Water Volume l 36 4 53 6 71 8 83 8 108 ...

Страница 89: ...72 21 48 28 31 35 35 51 03 EER at Max Airflow 20 7 21 1 20 3 22 5 20 7 21 5 21 7 19 7 Dimensions Depth mm 1050 1050 1050 1050 2200 2200 2200 2200 Height mm 2280 2280 2280 2280 2400 2400 2400 2400 Width mm 2200 2500 3100 3500 3000 4000 5000 6000 Mass Machine Operating kg 673 798 770 913 920 1108 1010 1225 1815 2289 2503 3184 3052 3914 3571 4600 Unit Water Volume l 124 6 143 2 188 2 214 9 474 5 681 ...

Страница 90: ... 8 25 1 28 7 6 6 9 7 13 2 15 3 Water Flow Rate l s 0 95 1 43 1 92 2 28 2 92 3 40 4 34 4 99 1 12 1 68 2 24 2 67 gpm 15 1 22 7 30 4 36 2 46 2 53 8 68 8 79 1 17 7 26 6 35 5 42 3 Pressure Drop 3 kPa 123 1 126 7 108 6 116 2 98 4 109 5 108 9 100 6 124 8 134 2 110 3 116 8 ftH2O 41 2 42 4 36 3 38 9 32 9 36 6 36 4 33 7 41 8 44 9 36 9 39 1 Fan Motor Centrifugal Quantity x Motor Size kW 1 x 3 35 1 x 3 70 2 x...

Страница 91: ...0 Height in 89 8 89 8 89 8 89 8 78 0 78 0 78 0 78 0 78 0 78 0 78 0 78 0 Width in 86 6 98 4 122 0 137 8 35 4 47 2 59 1 70 9 86 6 98 4 122 0 137 8 Mass Machine Operating kg 552 623 610 691 740 848 810 934 281 309 345 387 404 456 461 526 539 618 596 688 726 848 798 936 lbs 1217 1374 1344 1524 1631 1870 1786 2059 620 681 761 852 890 1006 1016 1158 1187 1363 1314 1516 1601 1868 1759 2064 Unit Water Vol...

Страница 92: ...24 3 29 3 36 9 44 3 9 7 13 6 18 3 21 3 Water Flow Rate l s 1 22 1 84 2 45 2 92 3 73 4 33 5 57 6 37 1 13 1 70 2 27 2 69 gpm 19 4 29 1 38 9 46 3 59 1 68 6 88 3 101 0 17 9 26 9 36 0 42 7 Pressure Drop 3 kPa 115 0 97 4 112 4 98 1 106 5 106 4 101 5 100 8 103 2 125 4 109 3 105 0 ftH2O 38 5 32 6 37 6 32 8 35 6 35 6 34 0 33 7 34 5 42 0 36 6 35 1 Fan Motor Centrifugal Quantity x Motor Size kW 1 x 3 35 1 x ...

Страница 93: ... 41 3 Height in 78 0 78 0 78 0 78 0 89 8 89 8 89 8 89 8 89 8 89 8 89 8 89 8 Width in 86 6 98 4 122 0 137 8 35 4 47 2 59 1 70 9 86 6 98 4 122 0 137 8 Mass Machine Operating kg 613 713 694 815 834 993 918 1099 357 399 438 498 519 599 590 683 699 819 786 925 945 1126 1041 1248 lbs 1350 1570 1530 1795 1838 2188 2023 2423 788 880 966 1097 1145 1320 1301 1505 1541 1806 1733 2038 2082 2482 2294 2751 Unit...

Страница 94: ... 5 217 9 274 9 5 8 8 5 11 5 13 4 16 4 20 1 25 1 30 9 Water Flow Rate l s 10 22 14 03 17 58 22 96 1 25 1 88 2 50 2 98 3 81 4 43 5 68 6 50 gpm 162 0 222 3 278 6 363 9 19 8 29 8 39 6 47 2 60 4 70 2 90 0 103 1 Pressure Drop 3 kPa 55 6 72 8 53 1 63 8 78 2 66 6 56 9 62 9 59 1 56 8 67 9 51 8 ftH2O 18 6 24 4 17 8 21 3 26 2 22 3 19 0 21 1 19 8 19 0 22 7 17 3 Fan Motor Centrifugal Quantity x Motor Size kW 6...

Страница 95: ...5 0 35 0 35 0 Height in 89 8 89 8 89 8 89 8 89 8 89 8 89 8 89 8 78 0 78 0 78 0 78 0 Width in 35 4 47 2 59 1 70 9 86 6 98 4 122 0 137 8 35 4 47 2 59 1 70 9 Mass Machine Operating kg 295 320 360 397 420 470 495 553 559 635 617 704 761 877 832 964 282 310 346 388 408 463 461 526 lbs 649 704 793 874 926 1035 1091 1219 1232 1399 1360 1551 1677 1933 1833 2125 620 682 763 854 898 1021 1016 1158 Unit Wate...

Страница 96: ...38 9 8 5 12 5 16 8 19 6 25 5 29 3 38 8 44 2 Water Flow Rate l s 4 12 4 79 6 14 7 05 1 59 2 38 3 16 3 77 4 80 5 57 7 17 8 25 gpm 65 3 75 9 97 4 111 7 25 2 37 7 50 0 59 7 76 1 88 3 113 7 130 8 Pressure Drop 3 kPa 60 2 57 6 65 9 55 9 69 3 61 5 64 2 56 4 57 7 65 6 53 9 67 4 ftH2O 20 1 19 3 22 1 18 7 23 2 20 6 21 5 18 9 19 3 22 0 18 0 22 5 Fan Motor Centrifugal Quantity x Motor Size kW 3 x 3 35 3 x 3 7...

Страница 97: ...3 41 3 41 3 41 3 Height in 78 0 78 0 78 0 78 0 78 0 78 0 78 0 78 0 89 8 89 8 89 8 89 8 Width in 35 4 47 2 59 1 70 9 86 6 98 4 122 0 137 8 35 4 47 2 59 1 70 9 Mass Machine Operating kg 317 352 390 442 461 531 523 603 619 724 695 815 849 1008 934 1115 359 400 443 506 519 599 597 695 lbs 698 775 860 974 1017 1169 1152 1330 1365 1596 1531 1796 1872 2222 2058 2458 790 882 977 1115 1145 1319 1316 1531 U...

Страница 98: ... 274 9 Water Flow Rate l s 5 14 6 01 7 68 8 80 13 28 18 18 22 82 29 97 gpm 81 5 95 2 121 7 139 4 210 5 288 1 361 7 475 0 Pressure Drop 3 kPa 60 3 51 1 55 8 65 9 72 0 58 6 52 8 75 5 ftH2O 20 2 17 1 18 7 22 0 24 1 19 6 17 7 25 3 Fan Motor Centrifugal Quantity x Motor Size kW 3 x 3 35 3 x 3 70 4 x 3 70 4 x 3 70 6 x 3 70 8 x 3 70 10 x 3 70 14 x 3 70 Speed 25Pa 0 10 in H2 O Maximum ESP rpm 1661 1780 13...

Страница 99: ...tion with incorrect phase rotation Check with a phase rotation meter Electrical Earthing Check that the earth is correctly bonded Remote ON OFF To ensure that the unit does not start doing the pre commissioning checks the remote on off should be in the OFF state Measure the voltage at the following points and record on the commissioning sheet Mains incoming Dedicated power supply Permanent supply ...

Страница 100: ...drop at full flow to the coil Binder insertion points are fitted to the unit for this purpose 2 Port Chilled Water and 2 Port Bypass Valves The chilled water valve is modulated proportionally to provide the required cooling with respect to cooling demand A bypass leg fitted with a further 2 port valve regulates system pressure drop The system pressure drop must be determined by the control system ...

Страница 101: ... is carried out should always be kept to a minimum and all necessary steps should be taken to minimise the risk and consequences of a fall Always follow local working from height practices and regulations Filters It is good practice to check filters at each maintenance visit Unit filter condition is monitored via the microprocessor The operational time is indicated along with the operational setpo...

Страница 102: ...odule to be removed Ensure the drain tube is reconnected when replacing the fan module IMPORTANT Fan Access To ensure suitable access for removing and maintaining fans that are located in the floor void a removable floor tile and support post must be provided when positioned in front of the unit Remove rail to release filter SmartCool Precision Air Conditioning Maintenance ...

Страница 103: ...ngs to lower the fan assembly to the rail for removal this will clear the fan inlet ring 3 Pull the fan assembly out An additional length of cable is provided to allow fan removal replacement Tie wraps should be carefully cut and replaced once the fan has been changed Precision Air Conditioning SmartCool Maintenance ...

Страница 104: ...ll slide out of the front of the unit as one complete assembly including the inlet ring 1 Remove external panel by removing fixings 2 Loosen fixings to release fan cartrige ready for removal 3 Pull fan assembly out 4 Rear fan can be accessed once the front fan is removed 5 Release fixings to rear far 6 Remove rear far SmartCool Precision Air Conditioning Maintenance ...

Страница 105: ...aintenance plus Check all electrical and plumbing connections for tightness Check system readings against those recorded on the original commissioning sheet and investigate significant differences Check the pressure drop of the water strainer external to unit If excessive clean the strainer Visually inspect the pipe and pipework insulation and check the pipework clamps are secure Check controller ...

Страница 106: ...available upon request Procedure When a component part fails a replacement part should be obtained through our Spares department If the part is considered to be under warranty the following details are required to process this requirement full description of part required including Airedale s part number if known the original equipment serial number an appropriate purchase order number A spares or...

Страница 107: ...Head Office Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel 44 0 113 2391000 Fax 44 0 113 2507219 E mail enquiries airedale com Web www airedale com ...