When working with any air conditioning units ensure that the electrical isolator is switched off prior
to servicing or repair work and that there is no power to any part of the equipment.
WARNING
Ensure that there are no other power feeds to the unit such as fire alarm circuits, BMS
circuits etc.
Electrical installation commissioning and maintenance work on this equipment must be
undertaken by competent and trained personnel in accordance with local relevant standards and
codes of practice.
CAUTION
Airedale recommends that appropriate personal protective equipment is used whilst installing,
maintaining and commissioning equipment.
IMPORTANT
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
injury or death, and could cause exposure to substances which have been determined by various
state agencies to cause cancer, birth defects or other reproductive harm. Read the installation,
operating and maintenance instructions thoroughly before installing or servicing this equipment.
WARNING
Please note that all gallon measurements in this manual are quoted in US gallons.
SmartCool™
Precision Air Conditioning
Introduction
Health and Safety
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
A full hazard data sheet, in accordance with COSHH regulations and OSHA Regulation and Local and State Codes, is
available should this be required.
Personal Protective Equipment
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer.
Remember do not perform a lift that exceeds your ability.
Pressure Equipment Directive (2014/68/EU) (UL 1995)
Minimum and Maximum Operation Temperature (Ts) and Pressure (Ps)
Waterside
Allowable Temperature Range (Ts), Ts =
Min 1°C* to Max 45°C** (Min 33.8 °F to Max 113 °F)
Maximum Allowable Pressure (Ps) Ps =
10 Barg (145psi)
*Based on the water temperature in the unit off state in the lowest permitted ambient temperature.
** Based on the maximum allowable ambient temperature in the unit off state.