7
TM SmartCool One 5057724 v1.0_08_2022
Nomenclature
Example:
S
O
09
D
003
C
L
C
S
L
-
0
S
Product Name
SmartCool
O
Product Variant
One - Dedicated Chilled
Water
09
Case Width
900mm / 35.4 in
12
1200mm / 47.2 in
15
1500mm / 59.1 in
18
1800mm / 70.9 in
22
2200mm / 86.6 in
25
2500mm / 98.4 in
31
3100mm / 122.0 in
35
3500mm / 137.8 in
30
3000mm / 118.1 in
40
4000mm / 157.5 in
50
5000mm / 196.9 in
60
6000mm / 236.2 in
D
Flow Configuration
Downflow
003-100
Nominal Cooling Capacity (kW/10)
C
Circuit One
Chilled Water Circuit
L
Coil type
Low Flow Coil suitable for ∆Ts from 9K to 12K
H
High Flow Coil suitable for ∆Ts from 6K to 9K
B
Coil Code
C
D
S
Case Height
Standard Height
X
Extended Height
L
Pipe Terminations
Left Hand Side
R
Right Hand Side
-
Separator
0
Power Supply
400V / 3Ph + N / 50Hz
3
460V / 3Ph / 60Hz
A
380V / 3Ph + N / 50Hz
Introduction
Designed specifically for high sensible applications such as Hyperscale & Colocation data centre applications, the
SmartCool One provides temperature and filtration control. The modular design of the SmartCool allows grouping of
differing model types and capacities to be installed side by side. The flexibility of this type of installation provides for
multi-circuit functionality.
Precision Air Conditioning System
The air conditioning equipment is designed specifically for precision temperature control and humidity monitoring
applications. It automatically monitors and controls cooling and filtering functions for the conditioned space. The system
is built to the highest quality engineering and manufacturing standards and is subject to a functional test prior to leaving
the factory.
Construction
The cabinet is manufactured using steel frame. Panels are completely removable to gain unequalled access during
installation as required. The galvanised sheet steel panels are coated with an epoxy baked powder paint to provide a
durable finish. Standard unit colour is Black Grey to RAL 7021. Cabinets are lined internally with various thickness of fire
resistant foam for thermal and acoustic insulation. The insulation density shall be no less than 75 kg/m³.
The cabinet doors are full height, hinged and key lock secured. The hinge arrangement allows flexible door opening and
removal for improved access. The unit design incorporates a series of M6 fixings to the top and bottom face to ease
customer ductwork connection and reduce installation time.
Precision Air Conditioning
SmartCool™
Introduction