![Mitsubishi Electric Q172CPU Скачать руководство пользователя страница 570](http://html.mh-extra.com/html/mitsubishi-electric/q172cpu/q172cpu_programming-manual_1811836570.webp)
APP - 9
APPENDICES
APPENDIX 2.1 Motion program setting errors (Stored in D9190)
The error codes, error contents and corrective actions for Motion program setting
errors are shown in Table 2.2.
Table 2.2 Motion program setting error list
Error code
stored in D9190
Error name
Error contents
Error processing
Corrective action
1
Parameter block No.
setting error
The parameter block No. is outside
the range of 1 to 64.
Execute the Motion program
with the default value "1" of
parameter block.
Set the parameter block No.
within the range of 1 to 64.
906
Axis No. setting
error
An unused axis of the system
setting is set to the Motion
program set in the SVST
instruction.
Positioning control does not
start.
Set the axis No. used in the
system settings.
3300
Number of control
program starts over
error
33 or more axis designation
programs are started
simultaneously.
Positioning control does not
start.
Set up to 32 programs as the
simultaneous execution
program.
3301
Number of
designation program
starts over error
17 or more control programs are
started simultaneously.
Positioning control does not
start.
Set up to 16 programs as the
simultaneous execution
program.
Содержание Q172CPU
Страница 1: ...Q173CPU N Q172CPU N Motion Controller SV43 Programming Manual Q172CPU Q173CPU Q172CPUN Q173CPUN ...
Страница 229: ...5 88 5 POSITIONING DEDICATED SIGNALS MEMO ...
Страница 447: ...7 186 7 MOTION PROGRAMS FOR POSITIONING CONTROL MEMO ...
Страница 535: ...8 88 8 AUXILIARY AND APPLIED FUNCTIONS MEMO ...
Страница 557: ...11 10 11 COMMUNICATIONS VIA NETWORK MEMO ...
Страница 559: ...12 2 12 MONITOR FUNCTION OF THE MAIN CYCLE MEMO ...