- 40 -
[
II
Restrictions ]
Address setting method
Pro
ce-
du-
res
Unit or controller
Address
setting
range
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit
IC
01 to 50
Assign the smallest address to
the main unit in the group.
In an R2 system with a sub BC
controller, make the settings for
the indoor units in the following
order.
(i) Indoor unit to be connected to
the main BC controller
(ii) Indoor unit to be connected to
sub BC controller 1
(iii) Indoor unit to be connected to
sub BC controller 2
Make the settings for the indoor
units in the way that the formula
"(i) < (ii) < (iii)" is true.
Port number setting is re-
quired by an R2 system.
00
Sub unit
Assign sequential numbers starting
with the address of the main unit in
the same group +1. (Main unit ad-
dress +1, main unit a2,
main unit a3, etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but unique ad-
dress to each of these units after
assigning an address to all indoor
units.
None of these addresses
may overlap any of the in-
door unit addresses.
00
3
MA
remote
control-
ler
Main
remote
controller
MA
No
settings
required.
-
Enter the same indoor
unit group settings on the
system controller as the
ones that were entered
on the MA remote con-
troller.
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made according to
the remote controller function se-
lection
4
Outdoor unit
OC
51 to 100 The sum of the smallest address of
the indoor units in the same system
and 50
To set the address to
100, set it to 50.
00
5
Auxiliary
unit
BC
controller
(main)
BC
52 to 100 Outdoor unit a 1
To set the address to
100, set it to 50.
If addresses that are
assigned to the main
BC controller overlap
any of the addresses
that are assigned to the
outdoor units or to the
sub BC controller, use
a different, unused ad-
dress within the setting
range.
The use of a sub BC
controller requires the
connection of a main
BC controller.
00
BC
controller
(sub)
BS
51 to 100 Assign an address that equals the
sum of the smallest address of the
indoor units that are connected to
the sub BC controller and 50.
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...