- 295 -
[
IX
Troubleshooting ]
(4) Errors that are not limited to a particular system
Error Code
Error definition and error detection method
6607
(Contin-
ued)
No ACK abnormality
The error is detected when no acknowledgement (ACK signal) is received after the
transmission. (eg. When the data is transmitted six times in a row with 30 seconds
interval, the error is detected on the transmission side.)
Note: The address/attribute appeared on the display on the remote control-
ler indicates the controller which did not provide the response (ACK).
Error
source ad-
dress
Error dis-
play
Detection
method
Cause
Check method and remedy
Address
which
should not
be existed
-
-
(1) Although the address of M-NET
remote controller has been
changed after the group is set
using M-NET remote controller,
the indoor unit is keeping the
memory of the previous ad-
dress.
The same symptom will appear
for the registration with SC.
(2) Although the address of LOSS-
NAY has been changed after the
interlock registration of LOSS-
NAY is made using M-NET re-
mote controller, the indoor unit is
keeping the memory of the pre-
vious address.
Delete unnecessary information of non-ex-
isting address which some indoor units
have.
Use either of the following two methods for
deletion.
1) Address deletion by M-NET remote
controller
Delete unnecessary address informa-
tion using the manual setting function of
M-NET remote controller. Refer to this
service handbook "4. [2]. Group set-
tings and interlock settings via the ME
remote controller 1. (3) Address dele-
tion".
2) Deletion of connection information of
the outdoor unit by the deleting switch
Note that this switch deletes all the
group information set via M-NET re-
mote controller and all the interlock
information of LOSSNAY and the in-
door unit.
Turn off the power source of the out-
door unit, and wait for 5 minutes.
Turn on the dip switch (SW2-2) on the
outdoor unit main board.
Turn on the power source of the out-
door unit, and wait for 5 minutes.
Turn off the power source of the out-
door unit, and wait for 5 minutes.
Turn off the dip switch (SW2-2) on the
outdoor unit main board.
Turn on the power source of the out-
door unit.
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...