- 184 -
[
VIII
Test Run Mode ]
(2) Example: PUHY-P234TGMU-A
(3) Sample calculation
15.88 [3/4"](30 m [98 ft])
15.88 [3/4"](10 m [32 ft])
6.35 [1/4"]
(10 m [32 ft])
9.52 [3/8"](10 m [32 ft])
9.52 [3/8"]
(10 m [32 ft])
9.52 [3/8"]
(10m [32 ft])
9.52 [3/8"]
(20 m [65 ft])
9.52 [3/8"]
(20 m [65 ft])
96 model
54 model
30 model
24 model
06 model
All the pipes in the figure are liquid pipes.
15.88 [3/4"] : 30 m [98 ft] + 10 m [32 ft] = 40 m [130 ft]
9.52 [3/8"] : 10 m [32 ft] + 2 0m [65 ft] + 20 m [65 ft] + 10 m [32 ft] + 10 m [32 ft] = 70 m [226 ft]
6.35 [1/4"] : 10 m [32 ft]
According to the above formula
The calculation result would be 15.44, and it is rounded up to the nearest 0.1.
The calculation result would be 540.7oz, and it is rounded up to the nearest 1 oz or 4 oz.
The final result will be as follows:
Amount of refrigerant to be charged (kg) = (0.2 X 40) + (0.06 X 70) + (0.024 X 10) + 3 = 15.44kg
Amount of refrigerant to be charged = 15.5kg
The final result will be as follows:
Amount of refrigerant to be charged (oz) = (2.15 X 130) + (0.65 X 226) + (0.26 X 32) + 106 = 540.7oz
Amount of refrigerant to be charged = 544oz or 541oz
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...