- 190 -
[
VIII
Test Run Mode ]
CAUTION
Do not release the extracted refrigerant into the air.
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
Start
SW2-4 ON
Put all indoor units in the test run mode
and run the units in cooling mode.
Gradually add refrigerant from the service
port on the low-pressure side
Gradually add refrigerant from
the service port on the low-
pressure side.
Gradually add refrigerant from the service
port on the low-pressure side
Has the initial start-up
mode been completed?
Has it been at least
30 minutes since start up?
SH 5K [9 F]
on all indoor units.
NO
NO
NO
NO
NO
NO
NO
NO
YES
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
Has the LEV opening been
stabilized on all indoor units? Note 1
Note 2
TH11 95 C [203 F]
Keep the unit running for 5 minutes after adjusting the refrigerant amount to determine its adequacy.
Gradually add refrigerant from the service
port on the low-pressure side
Adjustment complete
SW2-4 OFF Note 4
Keep the unit running for 5 minutes after adjusting the refrigerant amount to determine its adequacy.
Keep the unit running for 5 minutes after adjusting the refrigerant amount to
determine its adequacy.
*Refer to the previous page for Note 1-4 in the chart .
Does the following hold true?
TH11 100 C [212 F]
Does the following hold true?
10K [18 F]
SC16
30K [54 F]
Note 1
Does the following hold true?
Does the following hold true?
5K [9 F] SC11
Note 1
Does the following hold true?
30K [54 F]
SC16
?
Gradually draw out refrigerant from the
service port on the low pressure side.
Has the compressor
operating frequency
stabilized?
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...