- 17 -
[
II
Restrictions ]
II
Restrictions
[1] Types and Maximum allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions
in this manual.
2) Install the control cable at least 5cm[1-31/32"] away from the power supply cable to avoid noise interference. (Do
not put the control cable and power supply cable in the same conduit tube.)
3) Provide class-D grounding on the outdoor unit.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect the terminal block for transmission line to supply voltage of 208V or 230V. Doing so will damage
the electronic components on the terminal block.
6) Use 2-core shielded cables as control cables. (Marked with OK in the figure below) Use a separate 2-core control
cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor units that belong to
different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and malfunc-
tions. (Marked with NO in the figure below)
(2) Control wiring
Different types of control wiring are used for different systems.
Refer to section "[4] An Example of a System to which an MA Remote Controller is connected - [6] An Example of a Sys-
tem to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
[Types and maximum allowable length of cables]
Control lines are categorized into 2 types: transmission line and remote controller line. Use the appropriate type of cables
and observe the maximum allowable length specified for a given system. If a given system has a long transmission line
or if a noise source is located near the unit, place the unit away from the noise source to reduce noise interference.
1) M-NET transmission line
Cable type
Facility
type
All facility types
Type
Shielded cable CVVS, CPEVS, MVVS
Number of
cores
2-core cable
Cable size
Larger than 1.25mm
2
[AWG16]
Maximum transmission
line distance between the
outdoor unit and the far-
thest indoor unit
200 m [656ft] max.
Maximum transmission
line distance for central-
ized control and Indoor/
outdoor transmission line
(Maximum line distance
via outdoor unit)
500 m [1640ft] max.
*The maximum overall line length from the power supply unit on the transmission lines for
centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
NO
OK
TB3
TB7
TB3
TB7
TB3
TB7
TB3
TB7
multiple-core cable
2-core shielded cable
2-core shielded cable
Indoor unit
Indoor unit
Outdoor unit
Outdoor unit
Remote Controller
Remote Controller
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...