- 341 -
[
IX
Troubleshooting ]
Items to be checked
Phenomena
Remedy
[3]
Check whether
the inverter is
damaged.
*Perform this
check if an error
occurs immedi-
ately before or
after turning on
the compressor.
Perform the following:
(1) Reconnect the connector
that was removed in section
[1].
(2) Disconnect the compressor
wiring.
(3) Turn on SW1-1 on the com-
pressor INV board.
Operate the outdoor unit after
above steps.Check the inverter
output voltage.
*It is recommended to use the
tester used in the 9.[4] -5-(5)
IPM troubleshooting when
checking the inverter output volt-
age.
Measure voltage when the com-
pressor inverter output frequen-
cy is stable.
1) IPM/overcurrent breaker
trip
(4250 Detail code No.
101, 102, 103, 104, 105,
106, and 107)
Refer to item [5] for inverter circuit
trouble.
2) The voltage imbalance
across all wiring
There is a high possibility
of an inverter circuit error
if the voltage imbalance
across all wiring is great-
er than the larger of the
values represented by
5% or 5V.
3) No voltage imbalance
across all wiring
See item [2].
Proceed to item [5], however if
there is no problem in section [2].
Replace the compressor if there is
no problem in section [5].
[4]
Check whether
the inverter is
damaged.Per-
form this check
if an error oc-
curs during op-
eration.
Turn on the outdoor unit.
Check the inverter output volt-
age.
*It is recommended to use the
tester used in the 9.[4] -5- (5)
IPM troubleshooting when
checking the inverter output volt-
age.
*Measure voltage when the
compressor inverter output fre-
quency is stable.
1) The voltage imbalance
across all wiring
There is a high possibility
of an inverter circuit error
if the voltage imbalance
across all wiring is great-
er than the larger of the
values represented by
5% or 5V.
Refer to item [5] for inverter circuit
trouble.
2) No voltage imbalance
across all wiring
See item [2].
Proceed to item [5], however if
there is no problem in section [2].
Replace the compressor if there is
no problem in section [5].
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...