- 286 -
[
IX
Troubleshooting ]
2. Transmission error
Error
Code
Error definition and error detec-
tion method
Cause
Check method and remedy
6201
Remote controller board failure
An error occurs when the data
cannot be read normally from
the nonvolatile memory built in
on the remote controller.
Remote controller failure
Replace the remote controller.
6202
Remote controller board failure
An error occurs when the clock
function built in on the remote
controller does not work nor-
mally.
Remote controller failure
Replace the remote controller.
6600
Address overlaps
The error is detected when the
same address is transmitted
from different units.
Note: The address/attribute
appeared on the display
on the remote controller
indicates the controller
where an error oc-
curred.
Two or more remote controllers for
the outdoor units, the indoor units,
LOSSNAY, and the M-NET remote
controllers have the same address-
es.
<Example>
The error code 6600 "01" appeared
on the display on the remote control-
ler indicates that an error occurred in
No.1 unit.
Two or more units whose addresses
are 01 exist in the same system.
Search for the unit which has the same ad-
dress with that of the source of the trouble.
When the same address is found, turn
off the power of the outdoor unit,
LOSSNAY and the indoor unit for 5
minutes or more after changing the ad-
dress, and then turn them on it again.
6601
Unset polarity
The error detected when trans-
mission processor cannot dis-
tinguish the polarities of the
M-NET transmission line.
(1) No voltage is applied to the
M-NET transmission line that
G-50A is connected to.
(2) M-NET transmission line to
which G-50A is connected is
short-circuited.
Check if power is supplied to the M-NET
transmission line of the G-50A, and cor-
rect any problem found.
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...