- 282 -
[
IX
Troubleshooting ]
Temperature sensor failure (outdoor unit)
Error Code
Error definition and error
detection method
Cause
Check method and remedy
5101
Discharge
(TH11)
(TH12)
1. When a short (high
temperature intake) or
an open (low tempera-
ture intake) of the ther-
mistor is detected (the
first detection), the
outdoor unit stops,
turns to anti-restart
mode for 3 minutes,
and restarts when the
detected temperature
of the thermistor
2. When a short or an
open is detected again
(the second detection)
after the first restart of
the outdoor unit, the
outdoor unit stops,
turns to anti-restart
mode for 3 minutes,
and restarts in 3 min-
utes when the detect-
ed temperature is
within the normal
range.
3. When a short or an
open is detected again
(the third detection) af-
ter the previous restart
of the outdoor unit, the
outdoor unit makes an
error stop.
4. When a short or an
open of the thermistor
is detected just before
the restart of the out-
door unit, the outdoor
unit makes an error
stop, and the error
code "5101", "5103",
"5104", "5105",
"5106", or "5107" will
appear.
5. During 3-minute anti-
restart mode, prelimi-
nary errors will be dis-
played on the LED
display.
6. A short or an open de-
scribed above is not
detected for 10 min-
utes after the com-
pressor start, during
defrost mode, or for 3
minutes after defrost
mode.
(1) Thermistor failure
Check thermistor resistance.
5105
Piping
(TH5)
(2) Pinched lead wire
Check for pinched lead wire.
5106
Outdoor air
temperature
(TH6)
(3) Torn wire coating
Check wire coating.
5107
Piping
(TH7)
(4) A pin on the male connec-
tor is missing or contact
failure
Check connector.
(5) Disconnected wire
Check for wire.
(6) Thermistor input circuit
failure on the main board
Check the intake temperature of the
sensor with the LED monitor.
When the temperature is far different
from the actual temperature, replace
the control board.
TH11/TH12
TH5
TH6
TH7
Short is detection
Open detection
240 C [464 F] and above (0.57 k )
110 C [230 F] and above (0.4k )
110 C [230 F] and above (0.4k )
70 C [158 F] and above (1.14k )
0 C [32 F] and below (643 k )
-40 C [-10 F] and below (130 k )
-40 C [-40 F] and below (130 k )
-40 C [-40 F] and below (130 k )
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...