- 241 -
[
IX
Troubleshooting ]
1301
Abnormal low
pressure
When starting the com-
pressor from Stop Mode
for the first time if low-
pressure reads
0.098MPa [14psi] imme-
diately before start-up,
the operation immediate-
ly stops.
(1) Inner pressure drop due to
a leakage.
(2) Low pressure sensor fail-
ure
(3) Short-circuited pressure
sensor cable due to torn
outer rubber
(4) A pin on the male connec-
tor is missing.
(5) Disconnected wire
(6) Failure of the low pressure
input circuit on the control-
ler board
Refer to the section on troubleshoot-
ing the low pressure sensor.
Error Code
Error definition and error
detection method
Cause
Check method and remedy
Содержание PUHY-P168
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 38: ... 29 II Restrictions ...
Страница 42: ... 33 II Restrictions ...
Страница 46: ... 37 II Restrictions ...
Страница 50: ... 41 II Restrictions ...
Страница 54: ... 45 II Restrictions ...
Страница 58: ... 49 II Restrictions ...
Страница 75: ... 66 ...
Страница 99: ... 90 III Outdoor Unit BC Controller Components 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 101: ... 92 ...
Страница 111: ... 102 ...
Страница 113: ... 104 ...
Страница 126: ... 117 VI Refrigerant Circuit 1 Refrigerant Circuit Figure 119 2 Principal Parts and Functions 126 ...
Страница 127: ... 118 ...
Страница 134: ... 125 VI Refrigerant Circuit 3 CMB P104 and P108NU GB sub TH25 TH22 LEV3a CP Solenoid valves Block Check valves Block ...
Страница 145: ... 136 ...
Страница 147: ... 138 ...
Страница 185: ... 176 ...
Страница 187: ... 178 ...
Страница 241: ... 232 ...
Страница 243: ... 234 ...
Страница 366: ... 357 IX Troubleshooting ...
Страница 367: ... 358 ...
Страница 368: ... 359 X LED monitor display on the outdoor unit board 1 How to read the LED on the service monitor 361 ...
Страница 369: ... 360 ...