[2-10 Restrictions on Refrigerant Pipes ]
- 50 -
HWE14040
GB
(3) Size of the refrigerant pipe between the branches for connection to indoor units
(4) Size of the refrigerant pipe between the first distributor and the second distributor
(5) Size of the refrigerant pipe between the first distributor or the second distributor and outdoor units
Total capacity of the
downstream units
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
- 140
ø9.52 [3/8"]
ø15.88 [5/8"]
P141 - P200
ø9.52 [3/8"]
ø19.05 [3/4"]
P201 - P300
ø9.52 [3/8"]
ø22.2 [7/8"]
P301 - P400
ø12.7 [1/2"]
ø28.58 [1-1/8"]
P401 - P650
ø15.88 [5/8"]
ø28.58 [1-1/8"]
P651 - P800
ø19.05 [3/4"]
ø34.93 [1-3/8"]
P801 -
ø19.05 [3/4"]
ø41.28 [1-5/8"]
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
ø19.05 [3/4"]
ø34.93 [1-3/8"]
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
200 model
ø9.52 [3/8"]
ø22.2 [7/8"]
250 model
300 model
ø12.7 [1/2"]
ø28.58 [1-1/8"]
350 model
400 model
450 model
ø15.88 [5/8"]
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......