[5-2 Outdoor Unit Control ]
- 96 -
HWE14040
GB
5-2-7
Defrost Operation Control
(1) Starting the defrost operation
The defrost cycle will start when all of the three conditions (outside temperature, cumulative compressor operation time, and
pipe temperature) under <Condition 1>, <Condition 2>, or <Condition 3> are met.
1) Evaporating temperature (Te)
The defrost cycle will not start if other outdoor units are in the defrost cycle or until a minimum of 10 minutes have passed
since the completion of the last defrost cycle.
If 10 minutes have passed since compressor startup or since the completion of a defrost cycle, a forced defrost cycle can be
started by setting DIP SW4(913) to ON.
Even if the defrost-prohibit timer is set to 90 minutes, the actual defrost-prohibit time for the next defrost cycle is 50 minutes
if the last defrost cycle took 12 minutes.
All units in the heating mode will simultaneously go into the defrost cycle in a system with multiple units. The units that are
not in operation may or may not go into the defrost cycle, depending on the cumulative operation time of their compressors.
(2) Defrost operation
Condition 1
Condition 2
Condition 3
Outside temperature
(TH7)
-5ºC [23ºF] or above
-5ºC [23ºF] or below
Cumulative compressor
operation time
50 minutes or more
90 minutes or more if the defrost prohibit timer is set to 90.
250 minutes or more
Evaporating tempera-
ture (Te)
The evaporating temperature
has stayed below the tempera-
ture in the table below (Note1)
for 3 minutes
(Te
≤
1.1 × TH7 - 7.5) continued
for 3 minutes or [{1.5 + 0.02 x
(20+TH7)} > 63LS] continued
for 3 minutes
The evaporating temperature
has stayed below the tempera-
ture in the table below (Note1)
for 3 minutes
P200 - P400
P450- P500
SW4 (915) OFF
-13 ºC
-11 ºC
SW4 (915) ON
-8 ºC
-8 ºC
Compressor frequency
Model
Compressor frequency
P200 - P250 models
79 Hz
P300 - P400 models
107Hz
P450 - P500 models
129Hz
Outdoor unit fan
Stopped
SV1a
ON
SV5b
OFF (open)
21S4a OFF
21S4b, 21S4c
OFF
SV9
OFF
SV10,SV11
OFF (Closed)
LEV1 0
pulses
*1
*1. This value may be greater than 0 pulse depending on the 63LS and TH4 status.
LEV2
2000 pulses
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......