[8-4 Checking Transmission Waveform and for Electrical Noise Interference ]
- 250 -
HWE14040
GB
8-4
Checking Transmission Waveform and for Electrical Noise
Interference
8-4-1
M-NET
Control is performed by exchanging signals between the outdoor unit and the indoor unit (ME remote controller) through M-
NET transmission. Noise interference on the transmission line will interrupt the normal transmission, leading to erroneous op-
eration.
(1) Symptoms caused by noise interference on the transmission line
(2) Wave shape check
Wave shape check
Check the wave pattern of the transmission line with an oscilloscope. The following conditions must be met.
1) Small wave pattern (noise) must not exist on the transmission signal. (Minute noise (approximately 1V) can be generated by
DC-DC converter or the inverter operation; however, such noise is not a problem when the shield of the transmission line is
grounded.)
2) The sectional voltage level of transmission signal should be as follows.
Cause
Erroneous operation
Error code
Error code definition
Noise interference on
the transmission line
Signal is transformed and will be misjudged as the
signal of another address.
6600
Address overlap
Transmission wave pattern is transformed due to
the noise creating a new signal
6602
Transmission pro-
cessor hardware er-
ror
Transmission wave pattern is transformed due to
the noise, and will not be received normally leading
to no acknowledgement (ACK).
6607
No ACK error
Transmission cannot be performed due to the fine
noise.
6603
Transmission line
bus busy error
Transmission is successful; however, the acknowl-
edgement (ACK) or the response cannot be re-
ceived normally due to the noise.
6607
6608
No ACK error
No response error
Logic
Voltage level of the transmission line
0
V
HL
= 2.5V or higher
1
V
BN
= 1.3V or below
[With transmission]
[Without transmission]
No fine noise allowed
No fine noise
allowed
52
52
52
52
52
V
BN
V
HL
Logic "0"
Logic "1"
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......