[8-3 Refrigerant Control Problems ]
- 247 -
HWE14040
GB
8 Trou
ble
s
ho
oting
Bas
e
d on Obse
rved
Sy
mpto
ms
8-3-2
Units in the Heating Mode Do Not Operate at Expected Capacity.
1. Phenomena
Although heating operation starts with the normal remote controller display, the capacity is not enough.
2. Cause, check method and remedy
Cause
Check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure.
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual
pressure with self-diagnosis LED.
→
If the accurate pressure is not detected, check
the pressure sensor.
Refer to the following page(s). [8-5-1 Comparing
the High-Pressure Sensor Measurement and
Gauge Pressure](page 253)
Note: Higher inlet pressure by the high pressure sensor
than the actual pressure causes insufficient capac-
ity.
SW4 setting (SW6-10: OFF)
For how to read the SW settings, refer to the fol-
lowing page(s). [9-1-1 How to Read the
LED](page 289)
(2)
Check the difference between the condensing tem-
perature (Tc) and the target condensing tempera-
ture (Tcm) with self-diagnosis LED.
Note: Higher Tc than Tcm causes insufficient capacity.
SW4 setting (SW6-10: OFF)
For how to read the SW settings, refer to the fol-
lowing page(s). [9-1-1 How to Read the
LED](page 289)
Note: Protection
works
and
compressor frequency does
not rise even at lower Tc than Tcm due to high dis-
charge temperature and high pressure.
At high discharge temperature:
Refer to the following page(s).[7-3-1 Error Code
[1102]](page 171)
At high pressure:
Refer to the following page(s).[7-3-3 Error Code
[1302] (during operation)](page 173)
High pressure sensor
Low pressure sensor
ON
SW4
1
2
3
4
5
6
7
8
9
10
OFF
ON
SW4
1
2
3
4
5
6
7
8
9
10
OFF
Condensing temperature Tc
Target condensing temperature Tcm
ON
SW4
1
2
3
4
5
6
7
8
9
10
OFF
ON
SW4
1
2
3
4
5
6
7
8
9
10
OFF
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......