[5-1 Dipswitch Functions and Factory Settings ]
- 86 -
HWE14040
GB
(2) Additional dipswitch settings at time of shipment
Switch
Function
Function according to switch setting
Switch setting timing
Units that
require
switch
setting
(Note 2)
OFF (LED3 Unlit)
ON (LED3 Lit)
SW4
SW6-10:
OFF
1-10
1:ON, 0:OFF
Self-diagnosis/operation
monitor
Refer to the following page(s). [9 LED Status
Indicators on the Outdoor Unit Circuit
Board](page 289)
Anytime after power on
C
SW4
1-10
[0:OFF,
1:ON]
(Note 1)
SW6-10:ON
No.769
1000000011
Test run mode: ON/OFF
Stops all ICs
Sends a test-run sig-
nal to all IC
Anytime after power on
A
No.832
0000001011
Cumulative compressor
operation time deletion
Retained
Cleared
Any time after being energized (When
changed from OFF to ON)
C
No.848
0000101011
Continuous heating cycle
function
Disabled
Enabled
After being energized and while the com-
pressor is stopped
B
No.896
0000000111
Clearance of error
history
OC
Retained (IC/OC)
Deleted (IC/OC)
Anytime after power on (OFF
→
ON)
C
OS
Retained (OS)
Deleted (OS)
No.897
1000000111
High sensible heat opera-
tion setting
Depends on the combined setting with No.
900 (Note 4)
After being energized and while the com-
pressor is stopped
A
No.900
0010000111
High sensible heat opera-
tion setting
Depends on the combined setting with No.
897 (Note 4)
After being energized and while the com-
pressor is stopped
A
No.912
0000100111
Pump down function
Normal control
Pump down opera-
tion
After being energized and while the com-
pressor is stopped
A
No.913
1000100111
Forced defrost (Note 3)
Normal control
Forced defrost starts
10 minutes after the completion of de-
frost operation (OFF
→
ON) or 10 minutes
after compressor start-up (OFF
→
ON)
D
No.915
1100100111
Defrost start temperature
(Note 3)
P200 - P300:
-13°C [9°F]
P350 - P450:
-11°C [12°F]
-8°C [18°F]
Anytime after power on
B
No.916
0010100111
Defrost end temperature
(Note 3)
P200, P250:
10°C [50°F]
P300 - P450:
7°C [45°F]
5°C [41°F]
Anytime after power on
B
No.918
0110100111
Changes the defrost timer
setting (Note 3)
50 minutes
90 minutes
Anytime after power on (OFF
→
ON)
B
No.921
1001100111
Temperature unit display
°C
°F
Anytime after power on
C
No.922
0101100111
Refrigerant amount adjust-
ment
Normal control
Refrigerant amount
adjust mode
When the compressor is in operation (ex-
cept during initial startup/becomes inef-
fective 90 minutes after compressor
started up.)
A
No.932
0010010111
Heating backup
Disabled
Enabled
Anytime after power on
A
No.933
1010010111
Snow sensor setting
Effective only when
TH7
≤
5 is true or the
snow sensor contact
input is on.
Effective when TH7
≤
5 is true
Anytime after power on
C
No.934
0110010111
Snow sensor setting
Continuous fan op-
eration (FAN=50%)
Intermittent fan op-
eration (The fan op-
erates in the cycle of
being in operation at
100% capacity for 5
minutes and then
stops and remains
stopped for 30 min-
utes.)
Anytime after power on
C
No.964
0010001111
Target evaporation tem-
perature setting
Depends on the setting combination with No.
982 (Note 5)
Anytime after power on
A
No.972
0011001111
Automatic cooling/heating
mode (IC with the smallest
address)
Normal control
Automatic cooling/
heating mode
Before power on (After configuring the
setting, perform a power reset.)
A
No.982
0110101111
Target evaporation tem-
perature setting
Depends on the setting combination with No.
964 (Note 5)
Anytime after power on
A
No.988
0011101111
Refrigerant recovery/Evac-
uation (two-way valve/
LEV1 open)
Disabled
Enabled
After being energized and when units are
stopped
C
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......