[8-9 Troubleshooting Inverter Problems ]
- 266 -
HWE14040
GB
8-9-2
Checking the Inverter Board Error Detection Circuit
8-9-3
Checking the Compressor for Ground Fault and Coil Resistance Problems
8-9-4
Checking the Inverter for Damage at No-Load
Items to be checked
Phenomena
Remedy
(1)
Remove power supply.
1)
Overcurrent error
Error code: 4250
Detail code: No. 101, 104, 105, 106, and
107
Replace the INV board.
(2)
Disconnect the inverter
output wire from the ter-
minals of the INV board
(SC-U, SC-V, SC-W).
2)
Logic error
Error code: 4220
Detail code: No. 111
Replace the INV board.
(3)
Apply power supply.
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
(4)
Put the outdoor unit into
operation.
4)
IPM open
Error code: 5301
Detail code: No.119
Normal
Items to be checked
Phenomena
Remedy
Disconnect the compressor wir-
ing, and check the compressor
Meg, and coil resistance.
1)
Compressor Meg failure
Error if less than 1 M
Ω
.
Check that there is no liquid refrigerant
in the compressor.
If there is none, replace the compres-
sor.
2)
Compressor coil resistance failure
Coil resistance value of 0.72
Ω
(20°C [68°F]): P200, P250 models
Coil resistance value of 0.32
Ω
(20°C [68°F]): P300, P350 models
Coil resistance value of 0.30
Ω
(20°C [68°F]): P400, model
Coil resistance value of 0.43
Ω
(20°C [68°F]): P450, P500 models
Replace the compressor.
Items to be checked
Phenomena
Remedy
(1)
Remove power supply.
1)
Inverter-related problems are detected.
Connect the short-circuit connector to
CN6 or set SW001-1 to ON, and go to
8-9-2.
(2)
Disconnect the inverter
output wire from the ter-
minals of the INV board
(SC-U, SC-V, SC-W).
2)
Inverter voltage is not output at the termi-
nals (SC-U, SC-V, and SC-W)
Replace the INV board.
(3)
Disconnect the short-cir-
cuit connector from CN6
on the INV board.
3)
There is an voltage imbalance between
the wires.
Greater than 5% imbalance or 5V
Replace the INV board.
(4)
Apply power supply.
(5)
Put the outdoor unit into
operation.
Check the inverter output
voltage after the inverter
output frequency has sta-
bilized.
4)
There is no voltage imbalance between
the wires.
Normal
* Reconnect the short-circuit connec-
tor to CN6 or restore SW001 to its orig-
inal setting after checking the voltage.
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......