[2-4 M-NET Address Settings ]
- 22 -
HWE14040
GB
2-4
M-NET Address Settings
2-4-1
Address Settings List
1. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. Address setting is not required for a City Multi system that consists of a single refrigerant circuit (with some exceptions).
*2. To set the ME remote controller address to "200", set the rotary switches to "00".
*3. To set the outdoor unit address to "100," set the rotary switches to "50."
*4. Some indoor units have 2 or 3 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1, and the No.3
controller board address must equal to the No. 1 controller address and 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of
capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
*6. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the
setting range.
Unit or controller
Address setting
range
Setting method
Facto-
ry set-
ting
CITY MULTI in-
door unit
Main/sub unit
00,
01 to 50
*1*6
Assign the smallest address to the main indoor unit in the
group, and assign sequential address numbers to the rest
of the indoor units in the same group.
*4
00
M-NET adapter
M-NET control in-
terface
Free Plan adapt-
er
LOSSNAY, OA processing unit
Air handling kit
00,
01 to 50
*1*6
Assign an arbitrary but unique address to each of
these units after assigning an address to all indoor
units.
00
ATW
Booster Unit
Water Hex Unit
ME remote con-
troller
Main remote
controller
101 to 150
Add 100 to the smallest address of all the indoor units
in the same group.
101
Sub remote
controller
151 to 200
*2
Add 150 to the smallest address of all the indoor units
in the same group.
MA remote controller
No address settings required. (The main/sub setting must be made if 2
remote controllers are connected to the system.)
Main
CITY MULTI outdoor unit
00,
51 to 100
*1,*3,*6
Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same
refrigerant circuit are automatically designated as OC
and OS.
*5
00
System controller
Group remote
controller
201 to 250
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
201
System remote
controller
Assign an arbitrary but unique address within the
range listed on the left to each unit.
ON/OFF re-
mote controller
Assign an address that equals the sum of the smallest
group number of the group to be controlled and 200.
Schedule timer
(compatible
with M-NET)
Assign an arbitrary but unique address within the
range listed on the left to each unit.
202
Central con-
troller
AE-200
AG-150A
GB-50ADA
G(B)-50A
000,
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit. The address must
be set to "000" to control the K-control unit.
000
LM adapter
201 to 250
Assign an arbitrary but unique address within the
range listed on the left to each unit.
247
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......