[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
- 225 -
HWE14040
GB
7 Troub
le
sho
o
ting Using Erro
r
Cod
e
s
7-8-24
Error Code [6846]
1. Error
code
definition
Start-up time over
2. Error
definition and error detection method
Start-up time over The unit cannot finish start-up process within 4 minutes after power on.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Contact failure of indoor/outdoor unit connecting wire
Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of in-
door and outdoor units.
(2)
Diameter or length of indoor/outdoor unit connecting wire is out
of specified capacity.
Check diameter and length of indoor/outdoor
unit connecting wire. Total wiring length: 80
m (including wiring connecting each indoor
unit and between indoor and outdoor unit)
Also check if the connection order of flat ca-
ble is S1, S2, S3.
(3)
2 or more outdoor units have refrigerant address "0". (In case of
group control)
Check if refrigerant addresses are overlap-
ping in case of group control system.
(4)
Noise has entered into power supply or indoor/outdoor unit con-
necting wire.
Check transmission path, and remove the
cause.
Note: The descriptions above, 1)-4), are for
EA, Eb and EC.
*The check code in the parenthesis indicates
PAR-30MAA model.
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......