[8-9 Troubleshooting Inverter Problems ]
- 270 -
HWE14040
GB
8-9-9
Checking the Fan Inverter for Damage at No Load
Items to be checked
Phenomena
Remedy
(1)
Turn off breaker.
*Turn power off without fail.
1)
Within 30 seconds from the start of
operation, an error other than a posi-
tion error (5305, 5306) (detail code
132) is detected.
Change fan board.
(2)
Disconnect the connector
CNINV from the fan board.
2)
Less than 5V unbalance in the wir-
ing.
Change fan board.
(3)
Set fan board switch SW1-1 to
ON.
3)
No unbalanced voltage in the wiring.
After 30 second, detail code 132 is
produced and the system stops.
Normal
*After checking, return
SW1&CNINV.
(4)
Turn on breaker.
(5)
Operate unit.
After about 30 seconds under
no load with constant voltage
output, the code below will be
displayed indicating a position
error (5305, 5306).
Detail code: 132
Also, running with no load pro-
duces constant voltage of
about 160V.
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......