[7-5 Error Code Definitions and Solutions: Codes [3000 - 3999] ]
- 181 -
HWE14040
GB
7 Troub
le
sho
o
ting Using Erro
r
Cod
e
s
7-5
Error Code Definitions and Solutions: Codes [3000 - 3999]
7-5-1
Error Code [3121]
1. Error
code
definition
Out-of-range outside air temperature
2. Error
definition and error detection method
When the thermistor temperature of -28°C[-18°F] or below has continuously been detected for 3 minutes during heating op-
eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm-
istor temperature to determine when two outdoor units are in operation.)
The compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop. (The
error display needs to be canceled by setting the remote controller.)
Outdoor temperature error is canceled if the units stop during error stop. (The error display needs to be canceled by setting
the remote controller.)
3. Cause, check method and remedy
Check the following factors if an error is detected, without drop in the outdoor temperature.
<Reference>
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
(6)
Thermistor input circuit failure on the control
board
Check the intake temperature of the sensor with the LED
monitor.
When the temperature is far different from the actual temper-
ature, replace the control board.
TH7
Open detection
-40 C [ -40 F ] and below (130 k )
Short detection
110 C [230 F ] and above (0.4 k )
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......