[6-9 Evaluating and Adjusting Refrigerant Charge ]
- 134 -
HWE14040
GB
(2) Example: PUHY-P350YKB-A1
(3) Sample calculation
A
B
C
D
e
a
b
c
d
Indoor 1: P125
40 m
10 m
2: P100
10 m
5 m
3: P40
15 m
10 m
4: P32
10 m
10 m
5: P63
10 m
The total length of liquid pipe of each size is as follows:
ø12.7: A + e = 40 + 10 = 50 m
A: ø12.7
a: ø9.52
b: ø9.52
c: ø6.35
d: ø9.52
e: ø12.7
B: ø9.52
C: ø9.52
D: ø9.52
ø9.52: B + C + D + a + b + d = 10 + 15 + 10 + 10 + 5 + 10 = 60 m
ø6.35: c = 10 = 10 m
P40
P100
P125
P32
P63
=
+
+
+
+
+ 3.5
+
+
+
+
+ 3.5
+ 0
+ 0
(kg)
0 (m) x 0.26 (kg/m)
Additional
refrigerant charge
=
0 0
50
x 0.11 60
x 0.054
10
x 0.021
= 12.5 (12.45) kg
Total length of liquid
x 0.26 (kg/m)
0 (m) x 0.18 (kg/m)
Total length of liquid
x 0.18 (kg/m)
50 (m) x 0.11 (kg/m)
Total length of liquid
x 0.11 (kg/m)
60 (m) x 0.054 (kg/m)
Total length of liquid
x 0.054 (kg/m)
10 (m) x 0.021 (kg/m)
Total length of liquid
x 0.021 (kg/m)
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......