[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 192 -
HWE14040
GB
7-6-16
Error Code [4230] Detail Code 126
1. Error
code
definition
DCL temperature fault (Detail code 126)(outdoor unit)
2. Error
definition and error detection method
When DCL temperature that equals or exceeds 170˚C is detected (applicable to INV30YC only)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems](page 264)
Cause
Check method and remedy
(1)
Fan inverter board fault
Refer to the following page(s). [8-9-8 Checking the Fan Board Error Detection Circuit
at No Load](page 269)
Refer to the following page(s). [8-9-9 Checking the Fan Inverter for Damage at No
Load](page 270)
Refer to the following page(s). [8-9-10 Checking the Fan Inverter for Damage with
Load](page 271)
(2)
Outdoor unit fan fault
Check the outdoor unit fan for proper operation.
If there is a problem with fan operation, check the fan motor. Refer to the following
page(s). [8-9-7 Checking the Fan Motor for Ground Fault and Coil Resistance Prob-
lems](page 269)
(3)
DCL temperature sen-
sor connector contact
failure
Check the connector (CNTH) on the inverter board for proper connection.
(4)
DCL error
If the problem persists after restart, replace the DCL.
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......