[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 196 -
HWE14040
GB
7-6-20
Error Codes [4250, 4255, 4256] Detail Code 105
1. Error
code
definition
Overcurrent error due to short-circuited motor (Detail code 105)
2. Error
definition and error detection method
When a short is detected on the load side just before starting the inverter operation.
3. Cause, Check method and remedy
In the case of 4250
In the case of 4255 and 4256
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems](page 264)
7-6-21
Error Code [4250] Detail Codes 106 and 107
1. Error
code
definition
Instantaneous overcurrent (Detail code 106)
Overcurrent (effective value) (Detail code 107)
2. Error
definition and error detection method
When a current above the specified value is detected by the electric current sensor.
Refer to the relevant pages for the details of model names and the specified values.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems](page 264)
Cause
Check method and remedy
(1)
Short - circuited compressor
Refer to the following page(s).
[8-9-3 Checking the Compressor for Ground Fault
and Coil Resistance Problems](page 266)
(2)
Output wiring
Check for a short circuit.
Cause
Check method and remedy
(1)
Short - circuited fan motor
Refer to the following page(s).
[8-9-7 Checking the Fan Motor for Ground Fault and
Coil Resistance Problems](page 269)
(2)
Output wiring
Check for a short circuit.
Cause
Check method and remedy
(1)
Inverter output related
Refer to the following page(s).
[8-9-2 Checking the Inverter Board Error Detection Circuit](page 266)
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance Prob-
lems](page 266)
[8-9-4 Checking the Inverter for Damage at No-Load](page 266)
[8-9-5 Checking the Inverter for Damage during Compressor Operation](page
267)
[8-9-11 Checking the Installation Conditions](page 271)
Check the IGBT module resistance value of the INV board, if no problems are
found.
[8-9-15 Troubleshooting Problems with IGBT Module](page 273)
(2)
The model selection
switches (SW5-3 - 5-8) on
the outdoor unit are set in-
correctly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]](page
227)
Содержание PUHY-P1000
Страница 1: ......
Страница 11: ... 2 HWE14040 GB ...
Страница 27: ... 18 HWE14040 GB ...
Страница 40: ... 2 6 System Connection Example 31 HWE14040 GB 2 Restrictions ...
Страница 61: ... 52 HWE14040 GB ...
Страница 75: ... 66 HWE14040 GB ...
Страница 93: ... 84 HWE14040 GB ...
Страница 121: ... 112 HWE14040 GB ...
Страница 171: ... 6 11 Standard Operation Data Reference Data 162 HWE14040 GB ...
Страница 243: ... 7 9 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14040 GB ...
Страница 295: ... 8 13 Troubleshooting Problems Using the LED Status Indicators on the Outdoor Unit 286 HWE14040 GB ...
Страница 297: ... 288 HWE14040 GB ...
Страница 334: ......